FIR03-00510
| FIR-Aging Inspection | 10/13/2005 | 10/13/2005 | 10/19/2005 10:28:40 AM | | NR |
|
|
Mike will call it in next week
|
BLD05-01794
| FIRE-Final Inspection | 10/13/2005 | 10/13/2005 | 10/13/2005 4:50:23 PM | P | FAIL |
|
|
Same items as the previous inspection have not been corrected.
|
FIR05-00562
| INSP-Final Inspection | 10/13/2005 | 10/13/2005 | 10/13/2005 4:49:49 PM | P | PART |
|
|
Deficiencies for the 6" tie in have been corrected.
|
FIR05-00320
| INSP-Final Inspection | 10/11/2005 | 10/13/2005 | 10/13/2005 4:46:36 PM | P | PASS |
|
|
Hood system operated correctly.
|
BLD05-02147
| FIRE-Conference | 10/12/2005 | 10/13/2005 | 10/13/2005 2:36:08 PM | P | PART |
|
|
Incubator area is OK to occupy.
|
BLD05-00487
| FIRE-Final Inspection | 10/12/2005 | 10/13/2005 | 10/13/2005 2:35:16 PM | P | PART |
|
|
A temporary occupancy was given with Sam Rogers permission. The temp was given on the fire alarm system in the tenant space which is to be changed out to a new system with the concouse alarm upgrade. Sound levels on when the alarm was activated did not meet the 15db above ambient as per code. Life safety can be finaled when the alarm permit is finaled. I could not make "temporary" under the fire alarm permit since it is in the "review" status.
|
FIR05-00429
| INSP-Final Inspection | 10/13/2005 | 10/13/2005 | 10/13/2005 2:29:25 PM | P | PASS |
|
|
permit finaled
|
MIS05-00181
| FIR-Final | 10/12/2005 | 10/13/2005 | 10/13/2005 2:17:19 PM | P | PART |
|
|
A temporary occupancy was given. Mount fire extinguisher. Do not exceed 48" to top of the handle, Provide address numbers 4" minimum facing the street of a contrasting color, provide sticker at the main exit, provide approved hardware on the east exterior doors. See plans for my door hardware notes. Manual flush bolts on the inactive leaf approved by George Slane.
|
BLD05-01566
| FIRE-Final Inspection | 10/12/2005 | 10/13/2005 | 10/13/2005 1:23:30 PM | P | FAIL |
|
|
Remove brackets from rear exit door, provide panic hardware on the inactive leaf as per approved plans, provide approved hardware on the restroom doors and provide a fire extinguisher for the mezzanine.
|
BLD05-01349
| FIRE-Final Inspection | 10/13/2005 | 10/13/2005 | 10/13/2005 11:16:29 AM | P | PASS |
|
|
Fire life safety finaled
|
FIR05-00562
| INSP-Sprinkler Rough-in | 10/12/2005 | 10/13/2005 | 10/13/2005 11:02:07 AM | A | FAIL |
|
|
Inspection was for the 6" main. Need to fire caulk around the penatration to the fire riser room, provide additional clearance at thepenatrationthrough the CMU wall and provide a 4 way brace at the top of the 6" rise up piece in the future stock room.
|
FIR05-00445
| INSP-Final Inspection | 10/13/2005 | 10/13/2005 | 10/13/2005 10:51:01 AM | P | PASS |
|
|
Fire alarm permit finaled
|
FIR05-00617
| INSP-Sprinkler Rough-in | 10/13/2005 | 10/13/2005 | 10/13/2005 10:26:22 AM | P | PART |
|
|
Incubator area passed. See approved plans for specific location
|
FIR05-00429
| INSP-Final Inspection | 10/13/2005 | 10/13/2005 | 10/13/2005 12:00:00 AM | P | PASS |
|
|
Varsity Bar and Grill sprinkler permit finaled
|