ELE06-03820
| Final | 10/13/2006 | 10/13/2006 | 10/13/2006 4:22:52 PM | P | CANC |
|
|
curtis ###-#### called contr for info on job, he said u/g buried, so he will uncover and call back in for inspection. 370 asked contr to cancel pm inspection.
|
ELE06-03798
| Electrical Rough-In | 10/13/2006 | 10/13/2006 | 10/13/2006 4:02:51 PM | P | FAIL |
|
|
Phone #: ###-#### Internet Inspection Request from: DJ Carman called, left corr notice, nec 404.8 center operating handle shall not be over 6'-7", 312.5 all conductors entering enclosures shall have abrasion protection, 334.30 nm cable shall be secured within 12" of box and every 4 1/2', 300.4(A)&(D) edge of holes and nm cable shall be 1 1/4" from edge of framing members,210.52(A)(2) 2' wall in kitchen shall have recpt, BCC all make-up shall be done, box water heater, fans, outside nm cable
|
ELE06-03513
| Electrical Rough-In | 10/13/2006 | 10/13/2006 | 10/13/2006 3:22:52 PM | P | PART |
|
|
TRENCH INSPECTION - PAUL KLINDT; Phone #: ###-#### Internet Inspection Request from: Sean DeLacy ok to cover east side and elect room u/g, need to see u/g to light at south end
|
ELE06-03531
| Final | 10/13/2006 | 10/13/2006 | 10/13/2006 2:45:13 PM | P | FAIL |
|
|
lloyd; Phone #: ###-#### Internet Inspection Request from: Patricia Smith called, left message, corrctions not complete, shall not use ceiling grid wires for raceway support, bkr openings shall be closed, strap mc cable out of box, ckt directory shall be explicit, 370 put ok by corrected items on corr notice
|
ELE06-02311
| Permanent Service | 10/12/2006 | 10/13/2006 | 10/13/2006 2:14:45 PM | P | PASS |
|
|
Service inspection, please contact Dan, thank you; Phone #: ###-#### Internet Inspection Request from: Wendy Waters p/s u/g n ok for house panel only, contr needs to get ti permits
|
ELE06-03821
| Electrical Rough-In | 10/13/2006 | 10/13/2006 | 10/13/2006 1:53:51 PM | P | CANC |
|
|
###-#### curtis talked to contr, can't get in/out mall in pm, asked him to schedule am inspection
|
ELE06-03498
| Permanent Service | 10/13/2006 | 10/13/2006 | 10/13/2006 1:03:33 PM | P | FAIL |
|
|
Internet Inspection Request from: Latisha Peltier called,left correction notice, nec 250.24(A) a grounded service shall have a grounding electrode conductor connected to the grounded service conductor, 250.32(B) grounded conductor shall not be connected to equipment grounding conductor at sub-panel
|
ELE06-03805
| Electrical Rough-In | 10/13/2006 | 10/13/2006 | 10/13/2006 12:49:02 PM | P | CANC |
|
|
any questions please call Ed Schallock; Phone #: ###-#### Internet Inspection Request from: Jeff Radford wrong type inspection request, see t/s
|
ELE06-03805
| Temporary Service | 10/13/2006 | 10/13/2006 | 10/13/2006 12:48:28 PM | P | PASS |
|
|
any questions please call Ed Schallock; Phone #: ###-#### Internet Inspection Request from: Jeff Radford t/s u/g n ok
|
ELE06-02254
| Electrical Rough-In | 10/13/2006 | 10/13/2006 | 10/13/2006 12:13:19 PM | A | PART |
|
|
Scheduled by a contractor via Hello! on 10/13/2006 at 7:06:44 AM. Contact: ###-####. soffit lights 2nd story ok to cover
|
ELE06-03628
| Rough-In Permanent Service | 10/13/2006 | 10/13/2006 | 10/13/2006 10:43:27 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 10/13/2006 at 12:03:36 AM. Contact: ###-####. ceiling ok to cover, p/s, exst meter pak, n ok
|
ELE06-03805
| Electrical Rough-In | 10/12/2006 | 10/13/2006 | 10/13/2006 9:51:17 AM | A | FAIL |
|
|
any questions please call Ed Schallock; Phone #: ###-#### Internet Inspection Request from: Jeff Radford called contr, wrong type inspection request, no address, no job id sticker
|
ELE06-02672
| Final | 10/11/2006 | 10/13/2006 | 10/13/2006 9:33:21 AM | A | FAIL |
|
|
toni; Phone #: ###-#### Internet Inspection Request from: Patricia Smith called left corr notice,fee due, corrections not done,nec 406.4(D) receptacle faces shall be flush or project from faceplates,404.9 faceplates shall seat against finished surface, 408.4 circuit directory shall be clear, concise, and cpmplete, 348.30 fmc shall be securely fastened within 12" of box, 725.8 cl1,2,3 cable shall be supported by building structure, 406.8(B) wet location recpt shall have weather-proof enclosure whether or not attachment plug cap is inserted,110.3(B) equipment shall be installed according to instructions,fan switch and cover, 110.12(C) there shall be no damaged receptacles
|
ELE06-03206
| Final | 10/13/2006 | 10/13/2006 | 10/13/2006 8:39:28 AM | A | NH |
|
|
Scheduled by a contractor via Hello! on 10/13/2006 at 6:57:21 AM. Contact: ###-####. called, left message, left card
|
ELE06-03281
| Electrical Rough-In | 10/12/2006 | 10/13/2006 | 10/13/2006 8:30:45 AM | A | PART |
|
|
Please inspect B-wing underground early in AM if possible. Thanks!; Phone #: ###-#### Internet Inspection Request from: Jim Friend B-wing u/g under slab ok to cover anop
|
ELE06-03531
| Final | 10/12/2006 | 10/13/2006 | 10/13/2006 8:15:44 AM | A | NH |
|
|
lloyd; Phone #: ###-#### Internet Inspection Request from: Patricia Smith called said to call when can get in
|