Inspections for the day of: Friday, October 13, 2006.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-03820 Final10/13/200610/13/200610/13/2006 4:22:52 PMPCANC
curtis ###-#### called contr for info on job, he said u/g buried, so he will uncover and call back in for inspection. 370 asked contr to cancel pm inspection.
ELE06-03798 Electrical Rough-In10/13/200610/13/200610/13/2006 4:02:51 PMPFAIL
Phone #: ###-#### Internet Inspection Request from: DJ Carman called, left corr notice, nec 404.8 center operating handle shall not be over 6'-7", 312.5 all conductors entering enclosures shall have abrasion protection, 334.30 nm cable shall be secured within 12" of box and every 4 1/2', 300.4(A)&(D) edge of holes and nm cable shall be 1 1/4" from edge of framing members,210.52(A)(2) 2' wall in kitchen shall have recpt, BCC all make-up shall be done, box water heater, fans, outside nm cable
ELE06-03513 Electrical Rough-In10/13/200610/13/200610/13/2006 3:22:52 PMPPART
TRENCH INSPECTION - PAUL KLINDT; Phone #: ###-#### Internet Inspection Request from: Sean DeLacy ok to cover east side and elect room u/g, need to see u/g to light at south end
ELE06-03531 Final10/13/200610/13/200610/13/2006 2:45:13 PMPFAIL
lloyd; Phone #: ###-#### Internet Inspection Request from: Patricia Smith called, left message, corrctions not complete, shall not use ceiling grid wires for raceway support, bkr openings shall be closed, strap mc cable out of box, ckt directory shall be explicit, 370 put ok by corrected items on corr notice
ELE06-02311 Permanent Service10/12/200610/13/200610/13/2006 2:14:45 PMPPASS
Service inspection, please contact Dan, thank you; Phone #: ###-#### Internet Inspection Request from: Wendy Waters p/s u/g n ok for house panel only, contr needs to get ti permits
ELE06-03821 Electrical Rough-In10/13/200610/13/200610/13/2006 1:53:51 PMPCANC
###-#### curtis talked to contr, can't get in/out mall in pm, asked him to schedule am inspection
ELE06-03498 Permanent Service10/13/200610/13/200610/13/2006 1:03:33 PMPFAIL
Internet Inspection Request from: Latisha Peltier called,left correction notice, nec 250.24(A) a grounded service shall have a grounding electrode conductor connected to the grounded service conductor, 250.32(B) grounded conductor shall not be connected to equipment grounding conductor at sub-panel
ELE06-03805 Electrical Rough-In10/13/200610/13/200610/13/2006 12:49:02 PMPCANC
any questions please call Ed Schallock; Phone #: ###-#### Internet Inspection Request from: Jeff Radford wrong type inspection request, see t/s
ELE06-03805 Temporary Service10/13/200610/13/200610/13/2006 12:48:28 PMPPASS
any questions please call Ed Schallock; Phone #: ###-#### Internet Inspection Request from: Jeff Radford t/s u/g n ok
ELE06-02254 Electrical Rough-In10/13/200610/13/200610/13/2006 12:13:19 PMAPART
Scheduled by a contractor via Hello! on 10/13/2006 at 7:06:44 AM. Contact: ###-####. soffit lights 2nd story ok to cover
ELE06-03628 Rough-In Permanent Service10/13/200610/13/200610/13/2006 10:43:27 AMAPASS
Scheduled by a contractor via Hello! on 10/13/2006 at 12:03:36 AM. Contact: ###-####. ceiling ok to cover, p/s, exst meter pak, n ok
ELE06-03805 Electrical Rough-In10/12/200610/13/200610/13/2006 9:51:17 AMAFAIL
any questions please call Ed Schallock; Phone #: ###-#### Internet Inspection Request from: Jeff Radford called contr, wrong type inspection request, no address, no job id sticker
ELE06-02672 Final10/11/200610/13/200610/13/2006 9:33:21 AMAFAIL
toni; Phone #: ###-#### Internet Inspection Request from: Patricia Smith called left corr notice,fee due, corrections not done,nec 406.4(D) receptacle faces shall be flush or project from faceplates,404.9 faceplates shall seat against finished surface, 408.4 circuit directory shall be clear, concise, and cpmplete, 348.30 fmc shall be securely fastened within 12" of box, 725.8 cl1,2,3 cable shall be supported by building structure, 406.8(B) wet location recpt shall have weather-proof enclosure whether or not attachment plug cap is inserted,110.3(B) equipment shall be installed according to instructions,fan switch and cover, 110.12(C) there shall be no damaged receptacles
ELE06-03206 Final10/13/200610/13/200610/13/2006 8:39:28 AMANH
Scheduled by a contractor via Hello! on 10/13/2006 at 6:57:21 AM. Contact: ###-####. called, left message, left card
ELE06-03281 Electrical Rough-In10/12/200610/13/200610/13/2006 8:30:45 AMAPART
Please inspect B-wing underground early in AM if possible. Thanks!; Phone #: ###-#### Internet Inspection Request from: Jim Friend B-wing u/g under slab ok to cover anop
ELE06-03531 Final10/12/200610/13/200610/13/2006 8:15:44 AMANH
lloyd; Phone #: ###-#### Internet Inspection Request from: Patricia Smith called said to call when can get in