Inspections for the day of: Friday, October 13, 2006.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD06-01379 FIRE-Final Inspection10/13/200610/13/200610/13/2006 5:28:04 PMPFAIL
No approved plans and the fire extinguisher inspection has expired.
FIR06-00707 INSP-Final Inspection10/13/200610/13/200610/13/2006 3:18:13 PMPFAIL
wrong sample tubes installed and the duct detectors need the magnahelic test or relocated out of the 90 elbow
BLD06-02231 FIRE-Final Inspection10/12/200610/13/200610/13/2006 3:16:36 PMAFAIL
provide suite number #103, provide annual inspection for the fire extinguisher, relocate exit sign to infront of the breakroom door as shown on the approved plans and provide emergency lighting in the corridor in front of the breakroom as shown on the plans.
BLD06-02735 FIRE-Final Inspection10/12/200610/13/200610/13/2006 3:11:53 PMAFAIL
repair the exit signs and emergency lights, provide an exit sign at the transitiona wall between the open office and rear offices, provide a current inspection tag for the fire extinguisher, test the smoke evac system with the inspector and provide missing ceiling tiles.
FIR06-00632 INSP-Final Inspection10/12/200610/13/200610/13/2006 2:11:37 PMAFAIL
Did not perform inspection since the fire sprinkler work for the common walkway was not done yet. The new bulkhead wall is causing sprinkler coverage issues on the walkway side.
BLD06-02228 FIRE-Final Inspection10/12/200610/13/200610/13/2006 2:11:04 PMPFAIL
Did not perform inspection since the fire sprinkler work for the common walkway was not done yet. The new bulkhead wall is causing sprinkler coverage issues on the walkway side.
BLD06-02229 FIRE-Final Inspection10/12/200610/13/200610/13/2006 2:10:39 PMPFAIL
Did not perform inspection since the fire sprinkler work for the common walkway was not done yet. The new bulkhead wall is causing sprinkler coverage issues on the walkway side.
BLD06-02230 FIRE-Final Inspection10/12/200610/13/200610/13/2006 2:10:23 PMPFAIL
Did not perform inspection since the fire sprinkler work for the common walkway was not done yet. The new bulkhead wall is causing sprinkler coverage issues on the walkway side.
BLD06-02227 FIRE-Final Inspection10/12/200610/13/200610/13/2006 2:10:05 PMPFAIL
Did not perform inspection since the fire sprinkler work for the common walkway was not done yet. The new bulkhead wall is causing sprinkler coverage issues on the walkway side.
FIR06-00707 INSP-Final Inspection10/13/200610/13/200610/13/2006 11:33:20 AMPCANC
Duplicate inspection
BLD06-02188 FIRE-Final Inspection10/12/200610/13/200610/13/2006 11:28:52 AMAPASS
Life safety finaled
BLD06-01565 FIRE-Final Inspection10/12/200610/13/200610/13/2006 10:35:56 AMAFAIL
No life safety was done since the fire alarm permit failed
FIR06-00733 INSP-Sprinkler Rough-in/Hydro10/13/200610/13/200610/13/2006 9:55:59 AMAPASS
Dry system sprinkler piping ok to cover. I went over the requirement for resubmitting the fdc location with troy.
FIR05-00644 INSP-Conference10/12/200610/13/200610/13/2006 9:00:48 AMADONE
fire place and the stairwell combustible concealed spaced have been filled with insulation and sheetrocked. I went over the combustible eaves with both the fire sprinkler contractor and the general contractor
BLD06-02022 FIRE-Final Inspection10/12/200610/13/200610/13/2006 8:04:38 AMAPASS
life safety passed
FIR06-00669 INSP-Final Inspection10/12/200610/13/200610/12/2006 2:13:37 PMAPASS
permit finaled