FIR08-00454
| INSP-Final Inspection | 10/13/2008 | 10/13/2008 | 10/13/2008 4:55:15 PM | P | DEFR |
|
|
|
FIR08-00239
| INSP-Sprinkler Rough-in/Hydro | 10/13/2008 | 10/13/2008 | 10/13/2008 4:54:56 PM | P | PART |
|
|
See approved plans for locations inspected to date.
|
BLD08-00848
| Extend Permit 180 days | 10/13/2008 | 10/13/2008 | 10/13/2008 4:54:19 PM | P | FAIL |
|
|
See previous correction notice.
|
FIR07-00606
| INSP-Final Inspection | 10/13/2008 | 10/13/2008 | 10/13/2008 4:53:40 PM | P | NR |
|
|
Missing ceiling tile at three vestibules, missing escutcheons at two locations.
|
BLD07-00007
| FIRE-Final Inspection | 10/10/2008 | 10/13/2008 | 10/13/2008 4:52:12 PM | A | FAIL |
|
|
Project related fire alarm permit needs to pass final inspection prior to building life safety approval. Also noted 2 EM lights and one exit sign in need of repair, provide one fire extinguisher for the 2nd level prop storage area, missing drop ceilings at three vestibules, one missing sprinkler escutcheon at the south hall, noted two exit signs at the stage area above doors with locking hardware at the egress side.
|
FIR08-00255
| INSP-Final Inspection | 10/9/2008 | 10/13/2008 | 10/13/2008 4:48:05 PM | A | FAIL |
|
|
See red lined notes on plans at area A for locations in need of revision including horn and speaker/strobe devices.
|
FIR08-00440
| FIR-Aging Inspection | 10/13/2008 | 10/13/2008 | 10/13/2008 4:46:10 PM | | DONE |
|
|
Work in progress, construction underway.
|
BLD08-02078
| FIRE-Final Inspection | 10/10/2008 | 10/13/2008 | 10/13/2008 4:44:46 PM | A | PASS |
|
|
Items on previous correction notes completed, noted deadbolt at the back exit to be removed prior to structural final inspection as discussed.
|