Inspections for the day of: Tuesday, October 13, 2015.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE12-01287 ELE-Aging Inspection10/13/201510/13/201510/13/2015 2:38:24 PM DONE
No outstanding issues with service change. Contractor passed away. Final ok
ELE12-01287 Final10/13/201510/13/201510/13/2015 2:32:26 PMPPASS
No outstanding issues with service change. Final ok
ELE15-02165 Final10/13/201510/13/201510/13/2015 2:29:50 PMPPASS
Bob is the site contact Phone #: ###-#### Inspection requested via web by Kerri Hamilton Final ok
ELE15-03291 Temporary Service10/13/201510/13/201510/13/2015 1:54:08 PMPPASS
Phone #: ###-#### Inspection requested via web by daniel bibikov
t/s u/g n ok
ELE15-03280 Rough-In Permanent Service10/13/201510/13/201510/13/2015 1:15:43 PMPPASS
Phone #: ###-#### Inspection requested via web by Darryn Coburn Rough in ok cover p/s u/g n ok
ELE15-03282 Final10/13/201510/13/201510/13/2015 12:45:31 PMPCANC
Phone #: ###-#### Inspection requested via web by Will Sevy Needed temp service inspection
ELE15-03282 Temporary Service10/13/201510/13/201510/13/2015 12:44:49 PMPPASS
Phone #: ###-#### Inspection requested via web by Will Sevy
p/s u/g n ok
ELE15-03295 Temporary Service10/13/201510/13/201510/13/2015 12:32:56 PMPPASS
Cal Phone #: ###-#### t/s u/g n ok
ELE15-03286 Conference10/12/201510/13/201510/13/2015 12:14:31 PMADONE
request inspection to determine required scope of work for insurance company Phone #: ###-#### Inspection requested via web by David Nelson
Discussed scope of work of rewiring house due to fire damage.
BCC 4-05-31(A)- Unfused conductors shall not enter a structure. Fused disconnecting means shall be installed outdoor or immediately on interior of structure. Service change required.
All walls openned up due to fire shall be brought up to present code. Garage, living rm, kitchen, hall, entry.
All damaged wiring shall be repaired or replaced.
ELE15-02751 Final10/12/201510/13/201510/13/2015 11:19:27 AMAPASS
call ###-#### for access Phone #: ###-#### Inspection requested via web by David Nelson Final ok
ELE15-03242 Electrical Rough-In10/12/201510/13/201510/13/2015 11:00:37 AMAPASS
Underground inspection only. Please contact Jerry ###-#### with any questions. Phone #: ###-#### Inspection requested via web by Tracy Robertson
Central lot, feeder conduits underground rough in ok cover
ELE15-02407 Final10/12/201510/13/201510/13/2015 10:43:31 AMAPASS
garage code is 1976 enter Phone #: ###-#### Inspection requested via web by Brian Hughes Final ok
ELE15-03205 Rough-In Permanent Service10/13/201510/13/201510/13/2015 10:21:46 AMAPASS
Phone #: ###-#### Inspection requested via web by Bob Glenn Rough in ok cover p/s u/g n ok
ELE15-00180 Final10/12/201510/13/201510/13/2015 9:15:28 AMAPASS
garage code 0813 Phone #: ###-#### Inspection requested via web by cal crosby Final ok
ELE15-03283 Final10/12/201510/13/201510/13/2015 8:50:25 AMAFAIL
Phone #: ###-#### Inspection requested via web by steve ragan
110.12(A)- Unused openings shall be closed.
* Coolers have not been hooked up yet. Check disconnecting means.
408.4- Circuit directories shall be complete.