Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE13-01285 ELE-Aging Inspection10/13/201510/13/201510/13/2015 1:29:01 PM DONE
did drive by final ok
ELE13-01285 Final10/13/201510/13/201510/13/2015 1:28:17 PMPPASS
finalok did drive by
ELE13-01214 ELE-Aging Inspection10/13/201510/13/201510/13/2015 1:22:08 PM DONE
Greg will call this in soon
ELE15-03252 Electrical Rough-In10/13/201510/13/201510/13/2015 1:10:11 PMPPASS
Underground inspection Contact Travis @ ###-#### Phone #: ###-#### Inspection requested via web by Cathy Duchek u.ground secondary to temp. service ok to cover
ELE15-03278 Electrical Rough-In10/12/201510/13/201510/13/2015 10:53:35 AMAPASS
Concrete encased electrode inspection. Phone #: ###-#### Inspection requested via web by Andy Rose r/i grounding electrode ok
ELE15-03288 Final10/12/201510/13/201510/13/2015 10:39:44 AMAFAIL
Pam Carlson is the owner should you need access. Phone #: ###-#### Inspection requested via web by sam petterson wiring to heat pump ok wiring from heat pump to air handelers wired with TC-ER cable ran by TML. NEC 400.8(1)-flexable cords and cables shall not be used as a substitute for permenent wiring of a structure. OK if sleeved with raceway. This electrical work needs to be done by licensed electrical contractor.
ELE15-03118 Electrical Rough-In10/12/201510/13/201510/13/2015 9:55:12 AMAPASS
Phone #: ###-#### Inspection requested via web by Harvey Reyna r/i ok as per ERIC S. plumbing permits pulled
ELE15-02822 Conference10/12/201510/13/201510/13/2015 9:43:25 AMADONE
Phone #: ###-#### Inspection requested via web by Jim Williams discuss bonding and grounding electrode conductor for new service for 111 and 139. Asked Jim to drive 2 ground rods at each service and bond fire sprinkeler risers and sections of copper plumbing piping nearest service. OK to bring grounding electrode conductors into termination cabinet with nuetral disconnect link installed by factory.
GCE15-00141 GCE-Rough-In10/12/201510/13/201510/13/2015 8:58:43 AMAPASS
###-#### r/i floor heat upst. ok
GCE15-00144 GCE-Final10/12/201510/13/201510/13/2015 8:44:15 AMAPASS
Jess ###-#### final ok
ELE15-00830 Electrical Rough-In10/12/201510/13/201510/13/2015 7:43:39 AMPCANC
Contact: Jeremiah Goins - Final inspection for the 3rd floor please Phone #: ###-#### >> Inspection requested via web by Deb Gooden Inspection cancelled from web by: Deb Gooden
ELE16-01838 Electrical Rough-In10/12/201510/13/201510/13/2015 12:00:00 AMAPASS
SHQ Lvl 6 Z 1,2,3
Room 202,203,210 Phone #: ###-#### Inspection requested via web by Tom Betty r/i ok level 6 zone 2 and 3 (100% on slab on deck complete for all levels. r/i walls ok in rms. 202,203 and 210