Inspections for the day of: Thursday, October 13, 2016.
Number of inspections: 4
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE16-01838 Final10/12/201610/13/201610/13/2016 3:12:19 PMAPART
T/I Reinspection Level 2, 3, 4, 5, 6 Level 3 Stack 1 Office Furniture Phone #: ###-#### Inspection requested via web by Tom Betty Level 2- Lower ladder rack in server room not bonded.
Level 3- Low volt covers loose, North office broke MC above ceiling and cove light box open, MDF room UPS31B shall be placed to maintain work clearences on panel boards as noted in 110.26.
Level 4- Furniture low volt covers loose.
Level 5- Clear cables from all access panels installed formisc equipment above ceiling system.
Level 6- Server room upper ladder rack bonding not complete.
Level 7- Remove Otis temp power cord from wall located in elevator quad core east.
Temp occupy ok when core and shell ELE temp final granted.
ELE15-01348 Electrical Rough-In10/13/201610/13/201610/13/2016 3:02:15 PMPPASS
Level 1, headquarters, northwest corner columns. Call Frank Phone #: ###-#### Inspection requested via web by Brandon Robinson
Duplicate request. Area noted lighting rough in ok cover
ELE15-01348 Electrical Rough-In10/13/201610/13/201610/13/2016 3:01:05 PMPPASS
Level 1, headquarters, northwest corner columns. Call Frank Phone #: ###-#### Inspection requested via web by Brandon Robinson
Area noted lighting boxes rough in ok cover.
ELE15-01348 Final10/12/201610/13/201610/13/2016 2:59:59 PMANR
C/S Final Stair 1 and 2 Phone #: ###-#### Inspection requested via web by Tom Betty
Unable to final due to out egress lighting not complete at exits of stairways.
Items to complete for temp occupancy. 404.8(A)- Handle for switch handle on bus duct shall be max height of 6'7" on floors 7, 8, 9.
695.6(A)- Supply conductors and fire pump equipment shall be located where total seperation of other corridors and power sources of at least 2 hours. Only single layer of 5/8" dry wall on stairway walls exposed to fire pump room.
Interior stairways complete 1st floor to roof