FIR16-00502
| INSP-Supply line flush | 10/13/2016 | 10/13/2016 | 10/13/2016 3:08:20 PM | P | PASS |
|
|
Underground flush passed
|
BLD16-03742
| FIRE-Final Inspection | 10/13/2016 | 10/13/2016 | 10/13/2016 3:06:59 PM | P | FAIL |
|
|
Repair or remove the non-functional and non-required exit sign/emergency light and provide annual inspection for the fire extinguisher
|
BLD15-00371
| FIRE-Final Inspection | 10/13/2016 | 10/13/2016 | 10/13/2016 3:06:15 PM | P | FAIL |
|
|
Provide ADA single action hardware as discussed and provide annual inspection for the expired fire extinguishers.
|
FIR15-00683
| INSP-Final Inspection | 10/11/2016 | 10/13/2016 | 10/13/2016 1:45:56 PM | A | CANC |
|
|
Ron Phone #: ###-####
|
FIR15-00683
| INSP-Sprinkler Rough-in/Hydro | 10/11/2016 | 10/13/2016 | 10/13/2016 12:30:05 PM | A | PASS |
|
|
The overhead hydro tests passed. The forward flush passed. Interior corrections have been made. Need pressure relief valves, signage on bell and alarm interconnects for a final.
|
BLD16-00628
| FIRE-Final Inspection | 10/12/2016 | 10/13/2016 | 10/13/2016 11:14:17 AM | A | FAIL |
|
|
Life safety is ok but is being held up by issues with the project related fire alarm permit.
|
FIR16-00357
| INSP-Alarm Testing | 10/12/2016 | 10/13/2016 | 10/13/2016 11:13:17 AM | A | DONE |
|
|
Need to add smoke detector in the Nurses Station area, need to relocate two other smoke detectors away from air diffusers, one wall mount strobe was non-functional, audio was not temporal but march time, elevator recall was not tested or any of the new smoke detectors in the corridor system. Scott Arellano is ok with a 30 day temporary to allow time for the contractor to correct the audio as long as all other items have been corrected.
|
BLD16-02594
| FIRE-Final Inspection | 10/12/2016 | 10/13/2016 | 10/13/2016 9:54:14 AM | A | PASS |
|
|
life safety passed
|