BLD16-03786
| FIRE-Final Inspection | 10/13/2016 | 10/13/2016 | 10/13/2016 3:45:28 PM | P | PASS |
|
|
No fire sprinkler modifications, no fire alarm modifications, fire extinguishers are in place and will be tagged with current inspection tags. Final life fire safety inspection passed/complete.
|
FIR15-00198
| INSP-Alarm Testing | 10/13/2016 | 10/13/2016 | 10/13/2016 3:26:13 PM | P | CANC |
|
|
Alarm testing rescheduled for following day due to inspection load.
|
FIR16-00450
| INSP-Sprinkler Rough-in/Hydro | 10/13/2016 | 10/13/2016 | 10/13/2016 3:24:47 PM | P | PART |
|
|
Hydrostatic test complete for entire overhead fire sprinkler piping in building. Rough to cover inspection complete for overhead fire sprinkler piping. Level 1 overhead fire sprinkler piping approved for cover, level 2 overhead fire sprinkler piping located between levels approved for cover, overhead fire sprinkler piping located on level 2 that is in attic space cannot be covered until tenting inspection is performed. Level 3 overhead fire sprinkler piping cannot be covered until tenting inspection is complete. Will need to verify that an approved method has been accepted and installed to keep the pipe crossing the breezeway's from freezing, this will be verified at a later date.
|
FIR16-00508
| INSP-Sprinkler Rough-in/Hydro | 10/12/2016 | 10/13/2016 | 10/13/2016 3:16:09 PM | P | PART |
|
|
Hydrostatic test for overhead fire sprinkler piping complete for levels 1 and 2. Rough to cover inspection for overhead fire sprinkler piping complete, overhead fire sprinkler piping located on level 1 approved for cover, overhead fire sprinkler piping located on level 2 cannot be covered until tenting inspection is complete. The 2nd level has a balcony that is not on the approved drawings, this balcony is on the southside of the building located on the end, balcony needs a dry sidewall install for coverage, sidewall install will be verified during tenting inspection.
|
FIR16-00509
| INSP-Sprinkler Rough-in/Hydro | 10/12/2016 | 10/13/2016 | 10/13/2016 3:15:39 PM | P | PART |
|
|
Hydrostatic test for overhead fire sprinkler piping complete for levels 1 and 2. Rough to cover inspection for overhead fire sprinkler piping complete, overhead fire sprinkler piping located on level 1 approved for cover, overhead fire sprinkler piping located on level 2 cannot be covered until tenting inspection is complete. The 2nd level has a balcony that is not on the approved drawings, this balcony is on the southside of the building located on the end, balcony needs a dry sidewall install for coverage, sidewall install will be verified during tenting inspection.
|
BLD16-00727
| FIRE-Final Inspection | 10/13/2016 | 10/13/2016 | 10/13/2016 3:09:06 PM | P | PASS |
|
|
Previously noted item in regards to the northwest door hardware has been repaired, final life fire safety inspection passed/complete.
|
BLD14-01823
| FIRE-Final Inspection | 10/11/2016 | 10/13/2016 | 10/13/2016 12:22:45 PM | A | PART |
|
|
Partial final life fire safety complete, final fire sprinkler inspection is complete, final fire alarm inspection is complete, fire extinguishers are in place with current inspection tags. Building fire sub-panel reports to clubhouse main fire panel, life fire safety will be a partial pass until clubhouse is done and the inspection is finaled/passed.
|
BLD14-01820
| FIRE-Final Inspection | 10/11/2016 | 10/13/2016 | 10/13/2016 12:20:52 PM | A | PART |
|
|
Partial final life fire safety complete, final fire sprinkler inspection is complete, final fire alarm inspection is complete, fire extinguishers are in place with current inspection tags. Building fire sub-panel reports to clubhouse main fire panel, life fire safety will be a partial pass until clubhouse is done and the inspection is finaled/passed.
|
FIR15-00790
| INSP-Final Inspection | 10/13/2016 | 10/13/2016 | 10/13/2016 12:03:48 PM | A | PASS |
|
|
Final fire alarm inspection passed/complete
|
BLD16-01644
| FIRE-Final Inspection | 10/12/2016 | 10/13/2016 | 10/13/2016 9:47:07 AM | A | PASS |
|
|
Final fire sprinkler inspection complete, final fire alarm inspection complete, fire extinguisher is in common area with a current inspection tag. Final life fire safety inspection passed/complete.
|
FIR16-00612
| INSP-Final Inspection | 10/13/2016 | 10/13/2016 | 10/13/2016 9:45:58 AM | A | PASS |
|
|
Final fire alarm inspection passed/complete.
|
BLD16-02450
| FIRE-Final Inspection | 10/13/2016 | 10/13/2016 | 10/13/2016 9:44:38 AM | P | PASS |
|
|
No fire sprinkler modifications, no fire alarm modifications, fire extinguisher is in place with current inspection tag. Final life fire safety inspection passed/complete.
|
BLD16-02289
| FIRE-Final Inspection | 10/12/2016 | 10/13/2016 | 10/13/2016 9:41:39 AM | A | PASS |
|
|
Final fire sprinkler inspection complete, no fire alarm modifications, fire extinguishers are in place with current inspection tags, fire riser room was locked so I could not verify if building fire sprinkler inspection is current. Final life fire safety inspection passed/complete.
|
FIR15-00588
| INSP-Sprinkler Rough-in/Hydro | 10/13/2016 | 10/13/2016 | 10/13/2016 9:31:57 AM | A | PASS |
|
|
24 hour air test for the 2 parking garage dry systems complete.
|
FIR16-00322
| INSP-Sprinkler Rough-in/Hydro | 10/12/2016 | 10/13/2016 | 10/13/2016 8:42:16 AM | P | CANC |
|
|
Please call Jake when you are headed out, thanks! Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello Inspection cancelled from web by: Anthony Minichiello
|
BLD16-02888
| FIRE-Final Inspection | 10/12/2016 | 10/13/2016 | 10/13/2016 8:40:22 AM | A | PART |
|
|
Tenant needs to relocated product/equipment for setting up purposes into newly joined spaces (newly joined space is currently addressed as 1017, will need address verification at final inspection), more work in tenant space is to be done at a later date. Partial life fire safety inspection is complete, no fire sprinklers, smoke detectors are stand-alone, fire extinguishers are in place and will be inspected before complete life fire safety inspection request.
|