Inspections for the day of: Friday, October 13, 2017.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR17-00308 INSP-Final Inspection10/13/201710/13/201710/13/2017 1:10:21 PMPCANC
Final inspection request will be rescheduled for a later date per conversation with Jake, phone number ###-####.
BLD17-02848 FIRE-Final Inspection10/12/201710/13/201710/13/2017 1:09:02 PMAPASS
Fire sprinkler inspection complete, fire alarm inspection complete, fire extinguishers will be mounted in discussed locations. Final life fire safety inspection passed/complete.
FIR17-00518 INSP-Final Inspection10/13/201710/13/201710/13/2017 1:08:13 PMPPASS
Final fire alarm inspection for area of work passed/complete.
FIR17-00594 INSP-Sprinkler Rough-in10/12/201710/13/201710/13/2017 1:07:41 PMAPASS
Rough to cover inspection for overhead fire sprinkler in area of work complete, area of work approved for cover. Semi recessed fire sprinkler heads in area of work ar Central O-ring type heads that were recalled are still in place, all o-ring type heads will need to be replaced before final fire sprinkler inspection.
BLD17-00307 FIRE-Final Inspection10/12/201710/13/201710/13/2017 11:25:13 AMAPASS
Fire sprinkler inspection is complete, fire alarm inspection is complete, fire extinguishers are in place with current inspection tags. Final life fire safety inspection for area of work passed/complete.
BLD17-03524 FIRE-Final Inspection10/12/201710/13/201710/13/2017 10:30:06 AMAPASS
Fire extinguishers are in place with current inspection tags, fire sprinkler system has current inspection tag. Life fire safety inspection for TCO passed/complete.
FIR17-00440 INSP-Final Inspection10/12/201710/13/201710/13/2017 10:13:36 AMAPASS
Final fire sprinkler inspection passed/complete.
BLD16-03454 FIRE-Final Inspection10/12/201710/13/201710/13/2017 10:13:36 AMAPASS
Fire sprinkler inspection complete, fire alarm inspection complete, fire extinguisher will be mounted in discussed location. Final life fire safety inspection for area of work passed/complete.
FIR16-00688 INSP-Final Inspection10/12/201710/13/201710/13/2017 9:28:42 AMAPASS
Final fire alarm inspection for area of work passed/complete.
BLD17-00307 FIRE-Final Inspection10/12/201710/13/201710/13/2017 8:22:24 AMACANC
Duplicate inspection request, this request is cancelled.
FIR17-00524 INSP-Final Inspection10/12/201710/13/201710/13/2017 8:15:29 AMACANC
please call 1/2 hour prior Phone #: ###-#### >> Inspection requested via web by Rick Groom Inspection cancelled from web by: Rick Groom
FIR17-00586 INSP-Sprinkler Rough-in10/12/201710/13/201710/13/2017 12:00:00 AMAPASS
Passed on vesitbule.