Inspections for the day of: Monday, October 14, 2002.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR02-00373 INSP-Sprinkler Rough-in/Hydro10/10/200210/14/200210/14/2002 12:00:00 AMAFAIL
rough-in for the TI is ok but can not be finaled untill the shell is finaled 10/14/2002 4:25:30 PM
BLD02-00992 FIRE-Final Inspection10/10/200210/14/200210/14/2002 12:00:00 AMAPASS
fire life/safety finaled. The architect stated that the new wall above the ceiling is intended for security not a fire wall after I questioned the lack of fire smoke damper and cable tray holes 10/14/2002 10:50:35 AM
BLD02-01479 FIRE-Final Inspection10/11/200210/14/200210/14/2002 12:00:00 AMACANC
contractor (douge) stated that he did not call for an inspection. Nobody called so I'm cancelling it 10/14/2002 4:26:24 PM
FIR02-00325 INSP-Final Inspection10/11/200210/14/200210/14/2002 12:00:00 AMAFAIL
verify dedicated electrical circuit to FACP has been completed, clean up wiring in the FACP, verify batteries in FACP are supervised after the panel gets cleaned up, duct smoke detectors do nto activate the fie smoke dampers as per the review comments, change labeling on the new tamper switch 10/14/2002 10:48:58 AM
FIR02-00162 INSP-Final Inspection10/11/200210/14/200210/14/2002 12:00:00 AMAFAIL
Scheduled by a contractor via Hello! on 10/11/2002 at 14:18:55. Contact: ###-####. verify dedicated electrical circuit to FACP has been completed, clean up wiring in the FACP, verify batteries in FACP are supervised after the panel gets cleaned up, duct smoke detectors do nto activate the fie smoke dampers as per the review comments, change labeling on the new tamper switch 10/14/2002 10:49:08 AM
FIR02-00304 INSP-Sprinkler Rough-in10/14/200210/14/200210/14/2002 12:00:00 AMPFAIL
provide additional hangers in 1st floor corridor, provide 4 way eq bracing in the northwest corner of the 2nd floor, provide upright instead of a pendant head in the 1st floor electrical room, provide adequate sprinkler coverage over lobby/egress corridor on the 1st floor.
FIR02-00325 INSP-Final Inspection10/11/200210/14/200210/14/2002 12:00:00 AMPCANC
duplicate inspection. The contractor said he punched in the wrong button and forgot to cancell 10/14/2002 4:27:08 PM