Inspections for the day of: Friday, October 14, 2005.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR05-00565 INSP-Final Inspection10/14/200510/14/200510/14/2005 5:27:35 PMPFAIL
Several items need correction including spacing issues, some missing hangers, missing heads in two locations, see stamped plans for annotations.
FIR05-00654 INSP-Final Inspection10/14/200510/14/200510/14/2005 5:25:23 PMPPASS
Fire sprinkler finaled.
BLD05-02542 FIRE-Final Inspection10/14/200510/14/200510/14/2005 4:27:45 PMPFAIL
Need current inspection tags on the provided fire ext. and ceiling tile installed at the sprinkler head next to closet.
FIR05-00651 INSP-Final Inspection10/14/200510/14/200510/14/2005 3:41:19 PMPFAIL
Request for temp. is denied.
FIR05-00562 INSP-Final Inspection10/14/200510/14/200510/14/2005 3:34:18 PMPFAIL
Approved resubmitted plans are not available for inspection or verification of compliance.
BLD05-02157 FIRE-Final Inspection10/14/200510/14/200510/14/2005 2:26:52 PMAPASS
Door hardware and emergency lights have been repaired as required, fire life safety finaled.
BLD05-01523 FIRE-Final Inspection10/13/200510/14/200510/14/2005 1:26:25 PMAPASS
Life safety finaled.
FIR05-00089 INSP-Final Inspection10/13/200510/14/200510/14/2005 12:38:06 PMAFAIL
Alarms not completed for final, need to cut heads in drop ceiling area north exit corridor, cert. backflow preventers, sign and fill antifreeze system, eq FDC, perform forward flow test, provide sign at standpipe and flow test see note #29 and 30 on plan review, exterior wall needs to be built at riser for WPI, drain and FDC, install outside bell, this is not a comprehensive or all inclusive list of remaining items.
FIR05-00660 INSP-Sprinkler Rough-in10/13/200510/14/200510/14/2005 11:19:28 AMAFAIL
The yard post indicator as shown on approved plans is not installed, the north/south run and first thrust block are okay to cover.
FIR05-00627 INSP-Final Inspection10/13/200510/14/200510/14/2005 10:27:59 AMAPASS
Fire sprinkler work is acceptable, permit passed.
FIR05-00406 INSP-Final Inspection10/13/200510/14/200510/14/2005 9:33:47 AMACANC
mark; Phone #: ###-#### Cancel inspection per Mark due to scheduling conflict with the existing tenant for permission to alarm test, he will reschedule for next week.
FIR05-00654 INSP-Final Inspection10/13/200510/14/200510/14/2005 9:30:20 AMAFAIL
The heads installed are quick response, need to provide standard response heads as indicated by submittals and required by NFPA to match the existing heads in the same space, also need to attatch retaining straps to the beam at two arm over hangers.
MIS05-00159 FIR-Final10/13/200510/14/200510/14/2005 8:54:54 AMAPASS
Items on correction notice have been completed, life safety passed inspection.
FIR05-00459 INSP-Final Inspection10/13/200510/14/200510/14/2005 12:00:00 AMACANC
brian ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie brian anderson cancl
FIR05-00622 INSP-Final Inspection10/14/200510/14/200510/14/2005 12:00:00 AMPPASS
Fire sprinkler permit finaled.