FIR05-00565
| INSP-Final Inspection | 10/14/2005 | 10/14/2005 | 10/14/2005 5:27:35 PM | P | FAIL |
|
|
Several items need correction including spacing issues, some missing hangers, missing heads in two locations, see stamped plans for annotations.
|
FIR05-00654
| INSP-Final Inspection | 10/14/2005 | 10/14/2005 | 10/14/2005 5:25:23 PM | P | PASS |
|
|
Fire sprinkler finaled.
|
BLD05-02542
| FIRE-Final Inspection | 10/14/2005 | 10/14/2005 | 10/14/2005 4:27:45 PM | P | FAIL |
|
|
Need current inspection tags on the provided fire ext. and ceiling tile installed at the sprinkler head next to closet.
|
FIR05-00651
| INSP-Final Inspection | 10/14/2005 | 10/14/2005 | 10/14/2005 3:41:19 PM | P | FAIL |
|
|
Request for temp. is denied.
|
FIR05-00562
| INSP-Final Inspection | 10/14/2005 | 10/14/2005 | 10/14/2005 3:34:18 PM | P | FAIL |
|
|
Approved resubmitted plans are not available for inspection or verification of compliance.
|
BLD05-02157
| FIRE-Final Inspection | 10/14/2005 | 10/14/2005 | 10/14/2005 2:26:52 PM | A | PASS |
|
|
Door hardware and emergency lights have been repaired as required, fire life safety finaled.
|
BLD05-01523
| FIRE-Final Inspection | 10/13/2005 | 10/14/2005 | 10/14/2005 1:26:25 PM | A | PASS |
|
|
Life safety finaled.
|
FIR05-00089
| INSP-Final Inspection | 10/13/2005 | 10/14/2005 | 10/14/2005 12:38:06 PM | A | FAIL |
|
|
Alarms not completed for final, need to cut heads in drop ceiling area north exit corridor, cert. backflow preventers, sign and fill antifreeze system, eq FDC, perform forward flow test, provide sign at standpipe and flow test see note #29 and 30 on plan review, exterior wall needs to be built at riser for WPI, drain and FDC, install outside bell, this is not a comprehensive or all inclusive list of remaining items.
|
FIR05-00660
| INSP-Sprinkler Rough-in | 10/13/2005 | 10/14/2005 | 10/14/2005 11:19:28 AM | A | FAIL |
|
|
The yard post indicator as shown on approved plans is not installed, the north/south run and first thrust block are okay to cover.
|
FIR05-00627
| INSP-Final Inspection | 10/13/2005 | 10/14/2005 | 10/14/2005 10:27:59 AM | A | PASS |
|
|
Fire sprinkler work is acceptable, permit passed.
|
FIR05-00406
| INSP-Final Inspection | 10/13/2005 | 10/14/2005 | 10/14/2005 9:33:47 AM | A | CANC |
|
|
mark; Phone #: ###-#### Cancel inspection per Mark due to scheduling conflict with the existing tenant for permission to alarm test, he will reschedule for next week.
|
FIR05-00654
| INSP-Final Inspection | 10/13/2005 | 10/14/2005 | 10/14/2005 9:30:20 AM | A | FAIL |
|
|
The heads installed are quick response, need to provide standard response heads as indicated by submittals and required by NFPA to match the existing heads in the same space, also need to attatch retaining straps to the beam at two arm over hangers.
|
MIS05-00159
| FIR-Final | 10/13/2005 | 10/14/2005 | 10/14/2005 8:54:54 AM | A | PASS |
|
|
Items on correction notice have been completed, life safety passed inspection.
|
FIR05-00459
| INSP-Final Inspection | 10/13/2005 | 10/14/2005 | 10/14/2005 12:00:00 AM | A | CANC |
|
|
brian ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie brian anderson cancl
|
FIR05-00622
| INSP-Final Inspection | 10/14/2005 | 10/14/2005 | 10/14/2005 12:00:00 AM | P | PASS |
|
|
Fire sprinkler permit finaled.
|