Inspections for the day of: Tuesday, October 14, 2008.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR08-00677 INSP-Final Inspection10/14/200810/14/200810/16/2008 5:34:51 PMPPASS
Scope of fire sprinkler permit work passed final inspection.
FIR08-00279 INSP-Final Inspection10/14/200810/14/200810/14/2008 4:59:55 PMPPASS
UG fire supply line permit finaled.
FIR06-00620 INSP-Alarm Testing10/8/200810/14/200810/14/2008 4:58:15 PMAPART
UF heat detectors at the cleanroom areas tested acceptable, SD for door release at the north side okayed, two manual pulls and one heat detector at the service isle passed.
FIR08-00255 INSP-Final Inspection10/14/200810/14/200810/14/2008 4:19:43 PMPPART
One fire damper in up stairs storage area behind stage was not connected to fire alarm system, a module will be added to smoke detectors. All fire alarm testing completed in assembly area except as noted above. NFPA inspection report must be completed before complete final. KR
FIR08-00512 INSP-Final Inspection10/13/200810/14/200810/14/2008 2:36:40 PMPFAIL
Tampers and flow switch tested.No other testing completed, A/V in living room did not function.KR
FIR07-00663 INSP-Final Inspection10/13/200810/14/200810/14/2008 12:16:27 PMAPASS
All corrections made per last inspection. KR
BLD07-03070 FIRE-Final Inspection10/13/200810/14/200810/14/2008 11:57:11 AMAPASS
Items on correction notice have been completed, existing vault okayed per fire chief with provision of the alternative automatic fire-extinguishing system- IFC 903.3.1.1.1, and 904.2.
FIR08-00160 INSP-Final Inspection10/13/200810/14/200810/14/2008 11:53:01 AMAPASS
Fire sprinkler permit work passed final inspection. Noted existing vault coverage exempted with fire chief D. Hanneman's approval per IFC 2006 sec. 903.3.1.1.1 and 904.2 including the installed automatic fire extinguishing system.
FIR08-00441 FIR-Aging Inspection10/14/200810/14/200810/14/2008 9:47:45 AM DONE
Site visit confirmed construction underway, work in progress.
FIR08-00594 INSP-Final Inspection10/13/200810/14/200810/14/2008 9:46:10 AMAPASS
Fire alarm field test passed, permit finaled.
FIR08-00388 INSP-Final Inspection10/13/200810/14/200810/14/2008 9:44:46 AMAFAIL
Inspection failed due to several items including one painted head at the electrical room, leaking pendent at the pharmacy area, dry pendent heads are not yet installed at the coolers, missing escutcheon at the staff restroom, provide correct pipe hanger at the outside storage locker, need as-builts for field mods, PIV tamper is not correcly adjusted, waterflow switch needs adjustment, provide pitot guage for forward flow testing, need main control signage at the riser #1 and #2 shutoff valves.
FIR08-00507 INSP-Final Inspection10/13/200810/14/200810/14/2008 9:37:06 AMAFAIL
PIV tamper is not correctly adjusted, waterflow switch is not functional, noted ground fault at the panel after testing had started, inspection concluded until repairs are made.
FIR08-00279 INSP-Final Inspection10/13/200810/14/200810/13/2008 2:02:14 PMACANC
Richard Clark is your contact. Thanks. Phone #: ###-#### Internet Inspection Request from: Stan Beus Inspection cancelled from web by: Stan Beus