FIR08-00677
| INSP-Final Inspection | 10/14/2008 | 10/14/2008 | 10/16/2008 5:34:51 PM | P | PASS |
|
|
Scope of fire sprinkler permit work passed final inspection.
|
FIR08-00279
| INSP-Final Inspection | 10/14/2008 | 10/14/2008 | 10/14/2008 4:59:55 PM | P | PASS |
|
|
UG fire supply line permit finaled.
|
FIR06-00620
| INSP-Alarm Testing | 10/8/2008 | 10/14/2008 | 10/14/2008 4:58:15 PM | A | PART |
|
|
UF heat detectors at the cleanroom areas tested acceptable, SD for door release at the north side okayed, two manual pulls and one heat detector at the service isle passed.
|
FIR08-00255
| INSP-Final Inspection | 10/14/2008 | 10/14/2008 | 10/14/2008 4:19:43 PM | P | PART |
|
|
One fire damper in up stairs storage area behind stage was not connected to fire alarm system, a module will be added to smoke detectors. All fire alarm testing completed in assembly area except as noted above. NFPA inspection report must be completed before complete final. KR
|
FIR08-00512
| INSP-Final Inspection | 10/13/2008 | 10/14/2008 | 10/14/2008 2:36:40 PM | P | FAIL |
|
|
Tampers and flow switch tested.No other testing completed, A/V in living room did not function.KR
|
FIR07-00663
| INSP-Final Inspection | 10/13/2008 | 10/14/2008 | 10/14/2008 12:16:27 PM | A | PASS |
|
|
All corrections made per last inspection. KR
|
BLD07-03070
| FIRE-Final Inspection | 10/13/2008 | 10/14/2008 | 10/14/2008 11:57:11 AM | A | PASS |
|
|
Items on correction notice have been completed, existing vault okayed per fire chief with provision of the alternative automatic fire-extinguishing system- IFC 903.3.1.1.1, and 904.2.
|
FIR08-00160
| INSP-Final Inspection | 10/13/2008 | 10/14/2008 | 10/14/2008 11:53:01 AM | A | PASS |
|
|
Fire sprinkler permit work passed final inspection. Noted existing vault coverage exempted with fire chief D. Hanneman's approval per IFC 2006 sec. 903.3.1.1.1 and 904.2 including the installed automatic fire extinguishing system.
|
FIR08-00441
| FIR-Aging Inspection | 10/14/2008 | 10/14/2008 | 10/14/2008 9:47:45 AM | | DONE |
|
|
Site visit confirmed construction underway, work in progress.
|
FIR08-00594
| INSP-Final Inspection | 10/13/2008 | 10/14/2008 | 10/14/2008 9:46:10 AM | A | PASS |
|
|
Fire alarm field test passed, permit finaled.
|
FIR08-00388
| INSP-Final Inspection | 10/13/2008 | 10/14/2008 | 10/14/2008 9:44:46 AM | A | FAIL |
|
|
Inspection failed due to several items including one painted head at the electrical room, leaking pendent at the pharmacy area, dry pendent heads are not yet installed at the coolers, missing escutcheon at the staff restroom, provide correct pipe hanger at the outside storage locker, need as-builts for field mods, PIV tamper is not correcly adjusted, waterflow switch needs adjustment, provide pitot guage for forward flow testing, need main control signage at the riser #1 and #2 shutoff valves.
|
FIR08-00507
| INSP-Final Inspection | 10/13/2008 | 10/14/2008 | 10/14/2008 9:37:06 AM | A | FAIL |
|
|
PIV tamper is not correctly adjusted, waterflow switch is not functional, noted ground fault at the panel after testing had started, inspection concluded until repairs are made.
|
FIR08-00279
| INSP-Final Inspection | 10/13/2008 | 10/14/2008 | 10/13/2008 2:02:14 PM | A | CANC |
|
|
Richard Clark is your contact. Thanks. Phone #: ###-#### Internet Inspection Request from: Stan Beus Inspection cancelled from web by: Stan Beus
|