Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD13-02833 FIRE-Final Inspection10/11/201310/14/201310/14/2013 3:17:23 PMPFAIL
Correction notice items include; repair non-functional exit signs and EM lights on battery backup, post max occupant load sign at the bar area per review conditions, provide a current annual inspection for the existing fire sprinkler system, verify offsite monitoring of the fire alarm system is current.
BLD13-01229 FIRE-Final Inspection10/11/201310/14/201310/14/2013 3:13:16 PMAPART
Missing signage at the main entry/exit, discussed general conditions for life safety inspection.
BLD13-01695 FIRE-Final Inspection10/11/201310/14/201310/14/2013 3:11:00 PMANR
Project related fire sprinkler permit must be finaled prior to building fire life safety approval.
FIR13-00541 INSP-Sprinkler Rough-in10/11/201310/14/201310/14/2013 3:09:42 PMAPART
Okay to cover overhead fire sprinkler system modifications at the grid ceilings. Need to provide verification exisitng system is current with an annual inspection.