FIR15-00198
| INSP-Alarm Testing | 10/13/2016 | 10/14/2016 | 10/14/2016 4:39:41 PM | P | DONE |
|
|
Alarm testing complete for in-duct detectors with damper closing, electrical room smoke detectors and fire door release on levels 4, 3 and 2.
|
FIR15-00198
| INSP-Alarm Testing | 10/13/2016 | 10/14/2016 | 10/14/2016 4:39:16 PM | A | DONE |
|
|
Alarm testing complete for in-duct detectors with damper closing, electrical room smoke detectors and fire door release on levels 7,6 and 5.
|
FIR16-00464
| INSP-Supply line flush | 10/14/2016 | 10/14/2016 | 10/14/2016 4:36:21 PM | P | DONE |
|
|
Underground flush for fire sprinkler supply complete
|
FIR16-00336
| INSP-Sprinkler Rough-in | 10/13/2016 | 10/14/2016 | 10/14/2016 1:50:49 PM | A | PART |
|
|
Rough to cover inspection for overhead fire sprinkler piping complete, overhead fire sprinkler piping located between levels approved for cover, fire sprinkler piping located in attic spaces cannot be covered until tenting insualtion is installed.
|
FIR16-00036
| INSP-Final Inspection | 10/14/2016 | 10/14/2016 | 10/14/2016 1:22:29 PM | P | PASS |
|
|
Final underground inspection for fire sprinkler supply passed/complete.
|
FIR16-00036
| INSP-Supply line flush | 10/14/2016 | 10/14/2016 | 10/14/2016 1:21:37 PM | P | DONE |
|
|
Underground flush complete
|
BLD15-04217
| FIRE-Final Inspection | 10/13/2016 | 10/14/2016 | 10/14/2016 8:24:07 AM | A | PASS |
|
|
No fire sprinklers, no fire alarms, fire extinguishers are mounted with current inspection tags. Final life fire safety inspection pased/complete.
|