BLD19-01795
| FIRE-Final Inspection | 10/14/2019 | 10/14/2019 | 10/14/2019 4:10:22 PM | P | CANC |
|
|
Phone number provided for point of contact was not the correct phone number for Dennis, provide correct phone number for point of contact for proper coordination of inspection completion, this request is cancelled.
dennis Phone #: ###-####
|
BLD19-03335
| FIRE-Final Inspection | 10/14/2019 | 10/14/2019 | 10/14/2019 3:47:45 PM | P | CANC |
|
|
Called point of contact provided at 3:30PM and left a message, did not find area of work. Waited until 3:45PM for a call back but none was revieved, proceeded to next inspection, this request is cancelled and a new inspection request will need to be rescheduled.
Alex Phone #: ###-####
|
BLD16-03440
| FIRE-Final Inspection | 10/11/2019 | 10/14/2019 | 10/14/2019 3:39:47 PM | P | CANC |
|
|
Inspection request for fire alarms needs to be completed under the associated FIR permit, no the BLD permit. Per conversation with the point of contact listed this request is cancelled and the correct permit for the fire alarms will need to be requested for fire alarm inspections.
For Fire Alarm Final Phone #: ###-#### Inspection requested via web by Dillon Barresi
|
BLD17-00102
| FIRE-Final Inspection | 10/14/2019 | 10/14/2019 | 10/14/2019 3:36:46 PM | P | FAIL |
|
|
Povide permit for fire alarm install as discussed.
Final for Fire/Life Safety - TCUP Phone #: ###-#### Inspection requested via web by Dillon Barresi
|
BLD19-04086
| FIRE-Final Inspection | 10/14/2019 | 10/14/2019 | 10/14/2019 2:37:00 PM | P | PASS |
|
|
No fire sprinklers, fire alarm system is an outdated system that is not in service, reccomend to have fire alarm system updated or have old system removed if not required, smoke detectors are in place and are stand-alone, fire extinguishers are placed with current inspection tags. Final life fire safety inspection complete, signature provided on sign-off card.
Elisa Phone #: ###-####
|
FIR19-00263
| INSP-Sprinkler Rough-in/Hydro | 10/14/2019 | 10/14/2019 | 10/14/2019 11:24:01 AM | P | PART |
|
|
Rough to cover inspection for overhead fire sprinkler piping located above suspended ceiling, southwest level 1 complete, southwest level 1 approved for cover.
Robert Chambers is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
BLD18-02872
| FIRE-Final Inspection | 10/11/2019 | 10/14/2019 | 10/14/2019 11:18:50 AM | A | PASS |
|
|
Previously noted items have been corrected, fire sprinkler inspection is complete, no fire aalrm modifications, fire extinguisher is placed with a current inspection tag. Final life fire safety inspection for area of work complete.
RACHEL Phone #: ###-####
|
FIR19-00724
| INSP-Final Inspection | 10/11/2019 | 10/14/2019 | 10/14/2019 9:37:46 AM | A | PASS |
|
|
Final fire sprinkler inspection for area of work complete.
Adam Phone #: ###-####
|
FIR19-00724
| INSP-Sprinkler Rough-in | 10/11/2019 | 10/14/2019 | 10/14/2019 9:37:16 AM | A | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler piping in area of work complete, approved for cover.
Adam Phone #: ###-####
|
FIR19-00663
| INSP-Final Inspection | 10/10/2019 | 10/14/2019 | 10/14/2019 12:00:00 AM | P | PART |
|
|
Tested flow switch, pull, smoke, cell communicator and battery trouble. All worked properly. Sprinkler contractor was not present and sprinkler valve was shut so actual flow and tampers were not functionally tested. Once tested, this permit can be finaled. Phone #: ###-#### >> Inspection requested via web by Ken Webster
|