Inspections for the day of: Thursday, October 15, 1998.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD97-02488 INSP-Final Inspection10/14/199810/15/199810/15/1998 12:00:00 AMACANC
MIKE ###-#### PAINT BOOTH inspection was for the paint booth under BLD97-3293
BLD97-03293 INSP-Final Inspection10/15/199810/15/199810/15/1998 12:00:00 AMAFAIL
sway bracing, ground wire, signs for sprinkler valves, need to test interlocks
BLD98-00301 INSP-Final Inspection10/15/199810/15/199810/15/1998 12:00:00 AMPFAIL
rick ###-#### sprinkler heads, strobe needed, roll door inop
BLD98-02671 INSP-Final Inspection10/15/199810/15/199810/15/1998 12:00:00 AMPPASS
occ approved
BLD97-02083 INSP-Sprinkler Rough-in/Hydro10/15/199810/15/199810/15/1998 12:00:00 AMPFAIL
continued sprinkler rough-in, c/n forthcoming