Inspections for the day of: Friday, October 15, 2004.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE03-03581 Final10/14/200410/15/200410/15/2004 12:00:00 AMAPASS
contact: chris carmine; Phone #: ###-#### Internet Inspection Request from: Deb McCoy ok 10/15/2004 11:29:42 AM
ELE04-02782 Final10/14/200410/15/200410/15/2004 12:00:00 AMAPASS
contact: chris carmine; Phone #: ###-#### Internet Inspection Request from: Deb McCoy ok 10/15/2004 11:29:18 AM
ELE04-02818 Final10/14/200410/15/200410/15/2004 12:00:00 AMAPASS
contact: chris carmine; Phone #: ###-#### Internet Inspection Request from: Deb McCoy ok 10/15/2004 11:29:32 AM
ELE04-03054 Electrical Rough-In10/14/200410/15/200410/15/2004 12:00:00 AMAPART
berry-Note: pouring concrete at 5:00 am; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles u/g N end slab 4 floor boxes ok 10/15/2004 8:52:19 AM
ELE04-02751 Electrical Rough-In10/15/200410/15/200410/15/2004 12:00:00 AMAPART
conference ok met with M K
ELE03-03579 Final10/15/200410/15/200410/15/2004 12:00:00 AMAPASS
final ok was expired by mistake by J Frank
ELE04-02742 Electrical Rough-In10/15/200410/15/200410/15/2004 12:00:00 AMPPART
###-#### - mitch new part ok old part of house , kit over 50%n rule , and no violations retained e strips in plastic boxes and box fill called 10/15/2004 3:44:24 PM
ELE04-03149 Final10/13/200410/15/200410/15/2004 12:00:00 AMPPASS
Phone #: ###-#### Internet Inspection Request from: Dana Moyer ok called to verify fan boxes for 4 fans Tom will call me 10/15/2004 4:03:41 PM
ELE04-02951 Final10/15/200410/15/200410/15/2004 12:00:00 AMPPART
Scheduled by a contractor via Hello! on 10/15/2004 at 9:26:16 AM. Contact: ###-####. need to check on some listing of xray tube head 10/15/2004 4:55:25 PM
ELE04-03151 Permanent Service10/15/200410/15/200410/15/2004 12:00:00 AMPPASS
pat - Note: final for permanent service; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles p/s o/h rec. ok 10/15/2004 4:30:27 PM
ELE04-03192 Temporary Service10/15/200410/15/200410/15/2004 12:00:00 AMPFAIL
###-#### - john cor. posted called clean dirt from t/s and replace or repair burnt lug in meter base 10/15/2004 3:45:34 PM
ELE04-03191 Conference10/15/200410/15/200410/15/2004 12:00:00 AMPPART
david - ; Phone #: ###-#### Internet Inspection Request from: Linda Hartwell met with contractor is this a mobile home, 550, or 545 manufactured bld ? p/s panel is installed covering a jbox behind it, bus is contaminated with paint, and no lable stating amps, volts , 3 or 4 wire feed 10/15/2004 1:59:45 PM
ELE04-02852 Conference10/14/200410/15/200410/15/2004 12:00:00 AMPNH
cell ###-#### - nick Note: ; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called cell no response, left meeage on home phone 10/15/2004 2:20:45 PM
ELE04-02350 Electrical Rough-In10/15/200410/15/200410/15/2004 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 10/15/2004 at 7:25:48 AM. floor heat ok 10/15/2004 2:42:31 PM
ELE04-03187 Temporary Service10/15/200410/15/200410/15/2004 12:00:00 AMPFAIL
Phone #: ###-#### Internet Inspection Request from: Linda Hartwell cor. posted needs clearence for drop, terminate GEC at neutral bus, drive grd rod flush 10/15/2004 9:40:30 AM
ELE04-02870 Electrical Rough-In10/15/200410/15/200410/15/2004 12:00:00 AMPPASS
david; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles will need to check in at front counter and them know you need to go to the new smoking area. walls and ceiling ok 10/15/2004 9:40:56 AM