BLD07-01321
| FIRE-Final Inspection | 10/12/2007 | 10/15/2007 | 10/16/2007 11:45:44 AM | A | PASS |
|
|
Life safety inspection passed.
|
FIR07-00681
| INSP-Final Inspection | 10/15/2007 | 10/15/2007 | 10/15/2007 2:58:29 PM | P | PASS |
|
|
Fire sprinkler permit finaled.
|
FIR07-00107
| INSP-Sprinkler Rough-in/Hydro | 10/9/2007 | 10/15/2007 | 10/15/2007 2:57:35 PM | A | PART |
|
|
Hydrostatic test for the 2nd and 1st floor completed areas passed, noted pending resubmittals and ordinary temp heads at the vicinity of unit heaters need to be changed.
|
FIR07-00172
| INSP-Final Inspection | 10/12/2007 | 10/15/2007 | 10/15/2007 2:55:11 PM | A | PART |
|
|
Need to relocate one SD at the elevator equip. room, pressure switch at the preaction panel is not connected to the outside bell, zone 3 descriptors at monitoring need to be changed, FACP, duct detectors, elevator, sprinkler monitoring tested okay.
|
FIR07-00285
| INSP-Final Inspection | 10/12/2007 | 10/15/2007 | 10/15/2007 2:50:48 PM | P | FAIL |
|
|
Provide forward flow bypass as indicated on approved plans, preaction pressure switch is not connected to the outside bell, need 911 sign at bell, provide lockout for the switches to the air compressor, need to certify the DCVA and the RP, provide calc. stickers, tags, signage etc. at the riser, need signage and locks for the control valves at the antifreeze loop, provide as-builts for field changes, need final walkthrough completed.
|
FIR07-00327
| FIR-Aging Inspection | 10/15/2007 | 10/15/2007 | 10/15/2007 10:32:39 AM | | DEFR |
|
|
wip
|
BLD06-01253
| FIRE-Final Inspection | 10/12/2007 | 10/15/2007 | 10/15/2007 10:31:38 AM | A | PASS |
|
|
Life safety inspection completed acceptable.
|
FIR07-00681
| INSP-Sprinkler Rough-in | 10/12/2007 | 10/15/2007 | 10/15/2007 10:28:36 AM | A | PASS |
|
|
Fire sprinkler install completed satisfactory.
|