Inspections for the day of: Wednesday, October 15, 2008.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE08-01975 ELE-Aging Inspection10/15/200810/15/200810/16/2008 1:42:37 PM PART
stopped at site called contr to call for inspection when ready
ESC08-00467 General Inspection10/15/200810/15/200810/15/2008 3:06:19 PMPPASS
site ok side hill stabilized with straw and mat, bmp in place
ESC08-00741 General Inspection10/15/200810/15/200810/15/2008 3:02:18 PMPPART
site ok excavation work being done
ELE08-02801 Permanent Service10/15/200810/15/200810/15/2008 3:00:56 PMPFAIL
Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot corr called 230.24(A) 8ft clearence over roof for drop, shall grd or bond water pipi if metallic, 250.64(E) bond both ends of raceway for GEC, 240.24 panel set too high top breaker space over 6ft 7"
ELE08-02504 Rough-In Permanent Service10/15/200810/15/200810/15/2008 2:08:04 PMPFAIL
Any questions, please call Clay, the house is open. Thank You. Phone #: ###-#### Internet Inspection Request from: Clay Morgan corr called shall grd or bond metallic water pipe if present, 300.3(B) shall install equip grd in pvc to subpanel and remove other one, 314.20 all outside boxes shall be flush with conbustible material, 230.28 support mast at top, 300.4 nail plates inside outside edges, 250.24(A)(5) isolate neutral and bond equip bus at subpanel
ESC07-01522 General Inspection10/15/200810/15/200810/15/2008 1:26:25 PMPPART
ok
ELE08-00875 Electrical Rough-In10/15/200810/15/200810/15/2008 1:25:52 PMPPART
MORGAN CEILING COVER Phone #: ###-#### Internet Inspection Request from: Sean DeLacy So, and Ea. outside soffits ok
ELE08-02788 Rough-In Permanent Service10/15/200810/15/200810/15/2008 12:46:43 PMPNH
ready for inspection Phone #: ###-#### Internet Inspection Request from: gary batten notice posted called
ELE08-02503 Electrical Rough-In10/15/200810/15/200810/15/2008 10:14:09 AMAPASS
This is for ceiling cover up final to follow in the next day or two Phone #: ###-#### Internet Inspection Request from: Don Lustig ok
ESC08-00336 General Inspection10/15/200810/15/200810/15/2008 9:40:06 AMAPASS
ok
ELE08-01976 Final10/14/200810/15/200810/15/2008 9:39:33 AMAPASS
ray Phone #: ###-#### ok
ELE08-02671 Permanent Service10/15/200810/15/200810/15/2008 8:59:33 AMPPASS
jared Phone #: ###-#### p/s u/g rec. ok
ELE08-02267 Permanent Service10/14/200810/15/200810/15/2008 8:33:28 AMAPASS
Permanent service is shown to have already passed inspection. Idaho Power needs stickers on each meter socket. Phone #: ###-#### Internet Inspection Request from: Joe Thomas was done 09-22-08 p/s u/g new for house panel ok
ELE08-00086 ELE-Aging Inspection10/15/200810/15/200810/15/2008 7:40:18 AM CANC