BLD08-01900
| FIRE-Final Inspection | 10/13/2008 | 10/15/2008 | 10/20/2008 4:36:32 PM | P | CANC |
|
|
An upgrade agreement needs to be worked out between Angela and Mark Sentenno - life safety Phone #: ###-####
|
FIR08-00454
| INSP-Final Inspection | 10/15/2008 | 10/15/2008 | 10/15/2008 4:03:30 PM | P | PASS |
|
|
Permit finaled
|
FIR08-00454
| INSP-Supply line flush | 10/15/2008 | 10/15/2008 | 10/15/2008 4:02:59 PM | P | PASS |
|
|
Both underground supply line flushes passed
|
BLD08-00457
| FIRE-Conference | 10/15/2008 | 10/15/2008 | 10/15/2008 3:33:41 PM | P | DONE |
|
|
Per a telephone conversation with the general contractor the existing outside lights, with battery backup, will suffice for the exit discharge lighting.
|
FIR08-00329
| INSP-Final Inspection | 10/15/2008 | 10/15/2008 | 10/15/2008 3:31:39 PM | P | PASS |
|
|
Permit finaled
|
FIR08-00327
| INSP-Final Inspection | 10/15/2008 | 10/15/2008 | 10/15/2008 3:31:22 PM | P | PASS |
|
|
Permit finaled
|
FIR08-00328
| INSP-Sprinkler Rough-in | 10/15/2008 | 10/15/2008 | 10/15/2008 3:31:03 PM | P | PASS |
|
|
The sprinkler piping is ok to cover except the piping in the north side high area. This piping needs to have a re-inspection when the batt insulation is installed.
|
BLD08-01278
| FIRE-Final Inspection | 10/15/2008 | 10/15/2008 | 10/15/2008 3:11:55 PM | P | PASS |
|
|
fire life safety completed.KR
|
FIR08-00639
| INSP-Supply line flush | 10/15/2008 | 10/15/2008 | 10/15/2008 2:36:08 PM | P | PASS |
|
|
Flush Under ground FDC piping.KR
|
FIR08-00204
| INSP-Final Inspection | 10/15/2008 | 10/15/2008 | 10/15/2008 2:32:40 PM | P | FAIL |
|
|
The water has been turned off to the fire sprinkler system at the street and there is exposed cpvc piping that has not been installed per the installation manual for exposed piping. Basically it needs to be tight to the ceiling. There is also a question of heat in the smoking room on the west side of the building.
|
FIR08-00557
| INSP-Final Inspection | 10/15/2008 | 10/15/2008 | 10/15/2008 2:04:51 PM | P | FAIL |
|
|
All testing completed except for RTU4 duct smoke detector. Unit was off, couuld not test shut down. KR
|
FIR08-00188
| INSP-Final Inspection | 10/15/2008 | 10/15/2008 | 10/15/2008 2:00:13 PM | P | PASS |
|
|
Fire sprinkler permit finaled.KR
|
FIR08-00471
| INSP-Final Inspection | 10/14/2008 | 10/15/2008 | 10/15/2008 1:50:50 PM | P | FAIL |
|
|
Provide sticker on bell, provide inspection tag on riser, hydraulic sticker, space heads and cover the plastic supply piping and the cpvc riser piping as discussed. It does not appear that the underground supply has been flushed either.
|
FIR08-00471
| INSP-Supply line flush | 10/14/2008 | 10/15/2008 | 10/15/2008 1:22:40 PM | A | FAIL |
|
|
Provide sticker on bell, provide inspection tag on riser, hydraulic sticker, space heads and cover the plastic supply piping and the cpvc riser piping as discussed. It does not appear that the underground supply has been flushed either.
|
BLD08-02181
| FIRE-Final Inspection | 10/14/2008 | 10/15/2008 | 10/15/2008 9:41:34 AM | A | PASS |
|
|
Fire life safety completed.KR
|
BLD08-02030
| FIRE-Final Inspection | 10/14/2008 | 10/15/2008 | 10/15/2008 9:18:17 AM | A | PASS |
|
|
Life safety completed. KR
|
FIR08-00627
| INSP-Sprinkler Rough-in | 10/14/2008 | 10/15/2008 | 10/15/2008 9:07:51 AM | A | FAIL |
|
|
The PIV is located 12' from the building not the required 40'. The approved plans show 40'. Relocate the PIV or get fire dept approval for the new location.
|
BLD08-00664
| FIRE-Final Inspection | 10/14/2008 | 10/15/2008 | 10/15/2008 8:47:17 AM | A | PASS |
|
|
Permit finaled per notes of last inspection. KR
|
FIR08-00354
| INSP-Final Inspection | 10/15/2008 | 10/15/2008 | 10/15/2008 8:45:27 AM | P | PASS |
|
|
All corrections made per last inspection. KR
|
FIR08-00639
| INSP-Supply line flush | 10/14/2008 | 10/15/2008 | 10/15/2008 8:18:49 AM | A | NR |
|
|
Will call this permit in tomorrow. Can not shut down system to make final connection until fire watch is in place. KR
|