Inspections for the day of: Wednesday, October 15, 2008.
Number of inspections: 20
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD08-01900 FIRE-Final Inspection10/13/200810/15/200810/20/2008 4:36:32 PMPCANC
An upgrade agreement needs to be worked out between Angela and Mark Sentenno - life safety Phone #: ###-####
FIR08-00454 INSP-Final Inspection10/15/200810/15/200810/15/2008 4:03:30 PMPPASS
Permit finaled
FIR08-00454 INSP-Supply line flush10/15/200810/15/200810/15/2008 4:02:59 PMPPASS
Both underground supply line flushes passed
BLD08-00457 FIRE-Conference10/15/200810/15/200810/15/2008 3:33:41 PMPDONE
Per a telephone conversation with the general contractor the existing outside lights, with battery backup, will suffice for the exit discharge lighting.
FIR08-00329 INSP-Final Inspection10/15/200810/15/200810/15/2008 3:31:39 PMPPASS
Permit finaled
FIR08-00327 INSP-Final Inspection10/15/200810/15/200810/15/2008 3:31:22 PMPPASS
Permit finaled
FIR08-00328 INSP-Sprinkler Rough-in10/15/200810/15/200810/15/2008 3:31:03 PMPPASS
The sprinkler piping is ok to cover except the piping in the north side high area. This piping needs to have a re-inspection when the batt insulation is installed.
BLD08-01278 FIRE-Final Inspection10/15/200810/15/200810/15/2008 3:11:55 PMPPASS
fire life safety completed.KR
FIR08-00639 INSP-Supply line flush10/15/200810/15/200810/15/2008 2:36:08 PMPPASS
Flush Under ground FDC piping.KR
FIR08-00204 INSP-Final Inspection10/15/200810/15/200810/15/2008 2:32:40 PMPFAIL
The water has been turned off to the fire sprinkler system at the street and there is exposed cpvc piping that has not been installed per the installation manual for exposed piping. Basically it needs to be tight to the ceiling. There is also a question of heat in the smoking room on the west side of the building.
FIR08-00557 INSP-Final Inspection10/15/200810/15/200810/15/2008 2:04:51 PMPFAIL
All testing completed except for RTU4 duct smoke detector. Unit was off, couuld not test shut down. KR
FIR08-00188 INSP-Final Inspection10/15/200810/15/200810/15/2008 2:00:13 PMPPASS
Fire sprinkler permit finaled.KR
FIR08-00471 INSP-Final Inspection10/14/200810/15/200810/15/2008 1:50:50 PMPFAIL
Provide sticker on bell, provide inspection tag on riser, hydraulic sticker, space heads and cover the plastic supply piping and the cpvc riser piping as discussed. It does not appear that the underground supply has been flushed either.
FIR08-00471 INSP-Supply line flush10/14/200810/15/200810/15/2008 1:22:40 PMAFAIL
Provide sticker on bell, provide inspection tag on riser, hydraulic sticker, space heads and cover the plastic supply piping and the cpvc riser piping as discussed. It does not appear that the underground supply has been flushed either.
BLD08-02181 FIRE-Final Inspection10/14/200810/15/200810/15/2008 9:41:34 AMAPASS
Fire life safety completed.KR
BLD08-02030 FIRE-Final Inspection10/14/200810/15/200810/15/2008 9:18:17 AMAPASS
Life safety completed. KR
FIR08-00627 INSP-Sprinkler Rough-in10/14/200810/15/200810/15/2008 9:07:51 AMAFAIL
The PIV is located 12' from the building not the required 40'. The approved plans show 40'. Relocate the PIV or get fire dept approval for the new location.
BLD08-00664 FIRE-Final Inspection10/14/200810/15/200810/15/2008 8:47:17 AMAPASS
Permit finaled per notes of last inspection. KR
FIR08-00354 INSP-Final Inspection10/15/200810/15/200810/15/2008 8:45:27 AMPPASS
All corrections made per last inspection. KR
FIR08-00639 INSP-Supply line flush10/14/200810/15/200810/15/2008 8:18:49 AMANR
Will call this permit in tomorrow. Can not shut down system to make final connection until fire watch is in place. KR