Inspections for the day of: Wednesday, October 15, 2014.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR14-00344 INSP-Sprinkler Rough-in10/14/201410/15/201410/16/2014 5:29:34 PMPPART
Rough-in at 2nd floor building B completed. Items noted include; min spacing at unit C208, unfinished 2" main to mechanical room, obstructed sprinkler coverage at unit C202, fire blocking incompleted at some locations. Housekeeping, trash, mechanical rooms not yet finished.
FIR14-00394 INSP-Final Inspection10/15/201410/15/201410/15/2014 3:38:02 PMPPASS
Fire alarm permit work passed inspection. Permit finaled.
BLD14-02967 FIRE-Final Inspection10/15/201410/15/201410/15/2014 2:21:10 PMPPASS
Fire life safety passed provided tenant removes curtains at the non-required second exit or removes exit signage at this location. To be finished prior to structural final for verification at that time.
FIR14-00612 INSP-Sprinkler Rough-in10/14/201410/15/201410/15/2014 11:51:19 AMAPART
Rough-in inspections completed for the following areas; multipurpose gym, main only at the riser room thru to the north addition hallway, new multipurpose room 202, conference room 119, food bank 114. Verified corrections at the sanctuary mezzanine. Refer to plans for dated annotations.
BLD14-00920 FIRE-Final Inspection10/14/201410/15/201410/15/2014 10:30:02 AMAPASS
Fire life safety inspection okay for final pending directional arrows as discussed at two exit signs, remove keyed locking hardware at the conference room door. Items to be finished prior to structural final as agreed. Inspection passed.
FIR14-00385 INSP-Final Inspection10/15/201410/15/201410/15/2014 10:27:35 AMAPASS
Scope of fire sprinkler work passed final walkthrough and inspection. Permit finaled.
FIR14-00639 INSP-Sprinkler Rough-in10/14/201410/15/201410/15/2014 10:25:46 AMAPART
Fire sprinkler work at the grid ceilings in perimeter rooms as marked and dated on stamped plans approved for cover.