Inspections for the day of: Monday, October 15, 2018.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE18-03948 Electrical Rough-In10/15/201810/15/201810/15/2018 3:52:42 PMPPASS
CALL PRIOR TO ARRIVING IT IS LOCKED. Phone #: ###-#### Inspection requested via web by Hidajet Zahic
Final ok
ELE18-03948 Final10/15/201810/15/201810/15/2018 3:31:18 PMPPASS
CALL PRIOR TO ARRIVING IT IS LOCKED. Phone #: ###-#### Inspection requested via web by Hidajet Zahic
Final ok
ELE18-03948 Electrical Rough-In10/15/201810/15/201810/15/2018 3:27:28 PMPPASS
CALL PRIOR TO ARRIVING IT IS LOCKED. Phone #: ###-#### Inspection requested via web by Hidajet Zahic
Only addition to location is an oven, All electrical in existing kitchen area original to previous tenant. All receptacles that appear newer are GFCI protected. Contractor removed a microwave and extension cord kitchen area to avoid code issue. Oven rough in ok
ELE18-03952 Electrical Rough-In10/15/201810/15/201810/15/2018 3:22:22 PMPFAIL
Phone #: ###-#### Inspection requested via web by Jose Guerrero
210.52- No point measured a long floor line shall be more than 6' from a receptacle outlet. In nook first receptacle outlet more than 8' from end of cabinet. receptacles serving counter top areas do not count for general layout.
334.30- NM cable shall have supports not to exceed 4 1/2'. 14-2 to can over stairs hangs below truss with supports over 4 1/2'.
800.100(B)(2)- Single family dwelling units with grounded electrical systems shall have gounding conductors connected to grounding electrode system.
ELE18-03753 Rough-In Permanent Service10/14/201810/15/201810/15/2018 2:15:43 PMPPASS
Phone #: ###-#### Inspection requested via web by ERIC CENTERS
Raceway installed for future solar all labeled every 10' with junction in garage soffit.
Rough in ok cover p/s u/g n ok
ELE18-03920 Electrical Rough-In10/15/201810/15/201810/15/2018 1:44:30 PMPPASS
oops will be there around noon an make sure you have access Phone #: ###-#### Inspection requested via web by dennis mcneely Level 2 floor rough in ok cover
ELE18-02479 Electrical Rough-In10/15/201810/15/201810/15/2018 1:28:00 PMPPASS
Ceiling rough in inspection for level 12 CH2M at the One Capitol building
Contact Jon Novak
Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek
Level 12 office grid rough ok cover
ELE18-03533 Final10/14/201810/15/201810/15/2018 12:47:52 PMAPASS
Phone #: ###-#### Inspection requested via web by Ron Zimmerman Final ok
ELE18-03934 Permanent Service10/14/201810/15/201810/15/2018 12:32:59 PMAPASS
We Had To Move Service To New pole As Per Idaho Power New Pole Requirements And Powered New Modular Or Mobile Home.The Trailer Is Open And All Ready For Inspection Thanks Dave ###-#### Phone #: ###-#### Inspection requested via web by jason shifflett
Underground rough in ok cover
p/s o/h n ok
ELE17-02862 Electrical Rough-In10/15/201810/15/201810/15/2018 12:15:54 PMAPASS
Garage ceiling for insulation Phone #: ###-#### Inspection requested via web by Tom Betty
NEC 330.30 and 110.27- MC cable shall not be installed where subject to physical damage. Just outside meter area is a lower section of ceiling where MC located between 6'6" and 7'. If located below striker height this area shall be protected from damage from traffic and pedestrian traffic by fencing off.
Area of ceiling in parking garage ok to insulate.
ELE18-01588 Final10/14/201810/15/201810/15/2018 10:21:33 AMAFAIL
Phone #: ###-#### Inspection requested via web by ron spen cer
408.4- Circuit directory shall be complete.
410.16- Master closet flourescent shall clear storage shelf by 6" minimum.
ELE18-01590 Final10/14/201810/15/201810/15/2018 10:20:14 AMAFAIL
Phone #: ###-#### Inspection requested via web by ron spen cer
406.6- Up bathroom receptacle cover not installed due to tile blocks installation.
ELE18-03936 Rough-In Permanent Service10/14/201810/15/201810/15/2018 9:48:47 AMAFAIL
Phone #: ###-#### Inspection requested via web by Kevin Heideman
250.32(A)- Seperate buildings fed by feeders or branch circuits shall have a grounding electrode system installed.
250.68- Connections to grounding electrode system shall be accessible after drywall installed. Mudring.
250.94- Provisions shall be provided for a intersystem bond connected to a grounding electrode system.
300.4- nail plates needed in up east bedroom.
300.15- wiring for disposal shall terminate in a box. wires not in box.
ELE18-03935 Rough-In Permanent Service10/14/201810/15/201810/15/2018 9:44:43 AMAFAIL
Phone #: ###-#### Inspection requested via web by Kevin Heideman
250.32(A)- A seperate building or structure fed by feeders or branch circuits shall have a grounding electrode system installed.
250.68- Connection to grounding electrode sysem shall be accessible after drywall installed. Mudring.
250.94- Provisions shall be provided for a intersystem bond that shall connect to a grounding electode system.
300.4- nail plates needed under stair near switch.