Inspections for the day of: Tuesday, October 15, 2019.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-00601 Electrical Rough-In10/15/201910/15/201910/15/2019 2:30:48 PMPPART
2nd floor rooms wall cover. Danny is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen
Discussed if AFCI protection required. 210.12(C)- All 120 volt, single phase, 15 and 20 amp branch circuits suppying outlets and devices installed in guest rooms and guest suites of hotels and motels shall have AFCI protection described in 210.12(A)(1) thru (6).
Discussed if 1 siding with drywall is allowed.
As per Boise City ordinance 4-05-23
UNLAWFUL TO CONCEAL
It shall be unlawful for any person, to cover up or in any way conceal any electrical wiring, cables, conduits or other equipment until the same has been inspected and approved by an Electrical Inspector.
Room 223 Mock up- Rough in ok cover
ELE19-03927 Rough-In Permanent Service10/15/201910/15/201910/15/2019 1:46:08 PMPPASS
Phone #: ###-#### Inspection requested via web by Greg Traudt
Rough in ok cover p/s u/g n ok
ELE19-03488 Electrical Rough-In10/15/201910/15/201910/15/2019 11:25:11 AMAPASS
Please call Luke for inspection of phase 2 walls. Thanks. Phone #: ###-#### Inspection requested via web by Rafael Castillo
South of elevator to west and west side wall rough in ok cover
ELE19-03971 Electrical Rough-In10/14/201910/15/201910/15/2019 10:32:26 AMAPASS
Tenant is located at the south west end of the building. Doors will be open, Steve is the G.C. contact for the project, he is with Zelham. He is on site to answer any questions or call me, Kurt. Ready for wall rough in, some overhead. Phone #: ###-#### Inspection requested via web by Kurt Carlson
Unit located on south west corner of building. Unit has misc offices and a small conference rm. Wall rough in ok cover
ELE19-03927 Rough-In Permanent Service10/14/201910/15/201910/15/2019 9:55:42 AMAFAIL
Phone #: ###-#### Inspection requested via web by Greg Traudt
300.4- Wher NM cable is run thru bored holes that do not maintain 1 1/4" from framing surface they shall be protected from damage by nail plates.
334.23- NM cable run on trusses within 7' of attic access shall be protected by guard strips.
334.30- NM cable shall be secured within 8" of island receptacle.
ELE19-03897 Rough-In Permanent Service10/14/201910/15/201910/15/2019 9:03:27 AMAPASS
thank you! Phone #: ###-#### Inspection requested via web by Darryn Coburn
Rough in ok cover p/s u/g n ok