ELE19-00601
| Electrical Rough-In | 10/15/2019 | 10/15/2019 | 10/15/2019 2:30:48 PM | P | PART |
|
|
2nd floor rooms wall cover. Danny is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen Discussed if AFCI protection required. 210.12(C)- All 120 volt, single phase, 15 and 20 amp branch circuits suppying outlets and devices installed in guest rooms and guest suites of hotels and motels shall have AFCI protection described in 210.12(A)(1) thru (6). Discussed if 1 siding with drywall is allowed. As per Boise City ordinance 4-05-23 UNLAWFUL TO CONCEAL It shall be unlawful for any person, to cover up or in any way conceal any electrical wiring, cables, conduits or other equipment until the same has been inspected and approved by an Electrical Inspector. Room 223 Mock up- Rough in ok cover
|
ELE19-03927
| Rough-In Permanent Service | 10/15/2019 | 10/15/2019 | 10/15/2019 1:46:08 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Greg Traudt Rough in ok cover p/s u/g n ok
|
ELE19-03488
| Electrical Rough-In | 10/15/2019 | 10/15/2019 | 10/15/2019 11:25:11 AM | A | PASS |
|
|
Please call Luke for inspection of phase 2 walls. Thanks. Phone #: ###-#### Inspection requested via web by Rafael Castillo South of elevator to west and west side wall rough in ok cover
|
ELE19-03971
| Electrical Rough-In | 10/14/2019 | 10/15/2019 | 10/15/2019 10:32:26 AM | A | PASS |
|
|
Tenant is located at the south west end of the building. Doors will be open, Steve is the G.C. contact for the project, he is with Zelham. He is on site to answer any questions or call me, Kurt. Ready for wall rough in, some overhead. Phone #: ###-#### Inspection requested via web by Kurt Carlson Unit located on south west corner of building. Unit has misc offices and a small conference rm. Wall rough in ok cover
|
ELE19-03927
| Rough-In Permanent Service | 10/14/2019 | 10/15/2019 | 10/15/2019 9:55:42 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Greg Traudt 300.4- Wher NM cable is run thru bored holes that do not maintain 1 1/4" from framing surface they shall be protected from damage by nail plates. 334.23- NM cable run on trusses within 7' of attic access shall be protected by guard strips. 334.30- NM cable shall be secured within 8" of island receptacle.
|
ELE19-03897
| Rough-In Permanent Service | 10/14/2019 | 10/15/2019 | 10/15/2019 9:03:27 AM | A | PASS |
|
|
thank you! Phone #: ###-#### Inspection requested via web by Darryn Coburn Rough in ok cover p/s u/g n ok
|