Inspections for the day of: Tuesday, October 15, 2019.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTom Saunders
TitleELE-INSPECTOR
Phone #208-794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-03258 Electrical Rough-In10/10/201910/15/201910/15/2019 1:56:39 PMPCANC
Pre-release inspection in order to allow ID Power to reconnect service Phone #: ###-#### Inspection requested via web by BRS Permitting..

wrong inspection...needed permanent service inspection
ELE19-03258 Permanent Service10/15/201910/15/201910/15/2019 1:55:37 PMPPASS
Pre-release inspection in order to allow ID Power to reconnect service Phone #: ###-#### Inspection requested via web by BRS Permitting..
p/s u/g reconnect ok
ELE19-01954 Final10/15/201910/15/201910/15/2019 1:32:09 PMPPASS
call half hour before // joe Phone #: ###-####...ok to final
ELE19-02689 Electrical Rough-In10/15/201910/15/201910/15/2019 12:48:38 PMPCANC
I''m home today so just stop by. Please come between 3 and 4 though. Thanks! Phone #: ###-#### Inspection requested via web by Brad Downs...spoke with permit holder...ok to reschedule for next day first thing 8AM
ELE19-01739 Electrical Rough-In10/15/201910/15/201910/15/2019 12:25:49 PMPFAIL
trench depth for monument light direct bury wire Phone #: ###-#### Inspection requested via web by David McClellan...
1) trench for UF wire needs verified to proper depth...installed without inspection...T300.5
ELE19-02902 Electrical Rough-In10/15/201910/15/201910/15/2019 12:24:32 PMPFAIL
trench depth for monument light direct bury wire Phone #: ###-#### Inspection requested via web by David McClellan...
1) UF wire needs trench to proper depth...T300.5
ELE19-03503 Electrical Rough-In10/15/201910/15/201910/15/2019 12:23:01 PMPFAIL
Phone #: ###-#### Inspection requested via web by David McClellan...
1) fireplace shall be installed for rough-in inspection
2) manufacturers rating on connector used at panel for branch circuits is rated for no more than 2 NM cables-RC50
3) Foyer wiring - 210.52(I)...3ft wall space needs outlet..2 places
ELE19-03828 Final10/14/201910/15/201910/15/2019 10:41:19 AMAPASS
Phone #: ###-#### Inspection requested via web by Dean Gernaat...thank you..corrections made...ok to final
ELE19-03892 Rough-In Permanent Service10/14/201910/15/201910/15/2019 10:24:20 AMAPASS
Just west of Fairview/Five Mile intersection on the south side of Fairview. Phone #: ###-#### Inspection requested via web by Dan Jennings...
rough ok to cover
p/s u/g new ok
ELE19-03534 Final10/14/201910/15/201910/15/2019 9:53:49 AMAPASS
20A Circuit For Floor Heat In Master ; Guest Bathroom Phone #: ###-#### Inspection requested via web by Louis Keller...ok to final
ELE19-02845 Final10/14/201910/15/201910/15/2019 9:25:50 AMAFAIL
garage code 4141 Phone #: ###-#### Inspection requested via web by Emmet Bushman...
1) OCPD shall be no larger than required by nameplate rating on appliance,,oven
2) all appliances shall be operational..
disposal whip needs installed
ELE19-03752 Electrical Rough-In10/15/201910/15/201910/15/2019 8:38:31 AMAPASS
Underground electrical Inspection for satellite structure pour
Contact Travis Hust
Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek...ok to pour...base conduits and uffer ground in base