ELE02-03040
| Electrical Rough-In | 10/14/2002 | 10/16/2002 | 10/16/2002 12:00:00 AM | A | FAIL |
|
|
###-#### late pm cor. posted met with contractor 314.43, 134.16, 210.52(A) 250.104 (A)(1) 314.17(A) replace all boxes with broken clamps 10/16/2002 12:02:20 PM
|
ELE02-03080
| Electrical Rough-In | 10/15/2002 | 10/16/2002 | 10/16/2002 12:00:00 AM | A | FAIL |
|
|
Scheduled by a contractor via Hello! on 10/15/2002 at 14:12:42. Contact: ###-####. 314.16, 300.4(A)(1)and (D) 300.14, 110.14(B), 110.12(A) and314.17(A) replace boxes with unsed KOs and broken clamps 110.3(B) use approved tool for crimp sleeves
cor. posted called and $45.00 reinspection fee due 10/16/2002 12:56:11 PM
|
ELE02-03205
| Final | 10/15/2002 | 10/16/2002 | 10/16/2002 12:00:00 AM | A | PASS |
|
|
###-#### air conditioner ok 10/16/2002 3:25:43 PM
|
ELE02-03209
| Rough-In Permanent Service | 10/15/2002 | 10/16/2002 | 10/16/2002 12:00:00 AM | A | PART |
|
|
NEIL CELL # 794 -3948 u/g only 10/16/2002 11:01:32 AM
|
ELE01-03021
| Electrical Rough-In | 10/16/2002 | 10/16/2002 | 10/16/2002 12:00:00 AM | P | PART |
|
|
underground cover -east end of roadway -casey -###-#### ok 10/16/2002 5:14:33 PM
|
ELE02-03212
| Temporary Service | 10/16/2002 | 10/16/2002 | 10/16/2002 12:00:00 AM | P | FAIL |
|
|
###-#### cor. posted $45.00 fee due 250.52(A)(5), and 250.56 short grd rod shall install 2 grd rods met with contractor 10/16/2002 2:54:18 PM
|
ELE02-03202
| Permanent Service | 10/16/2002 | 10/16/2002 | 10/16/2002 12:00:00 AM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 10/16/2002 at 10:49:56. Contact: ###-####.
p/s o/h rec. ok for address 1420, and 1418 S Newport St there will be 2 meters now 10/16/2002 4:32:49 PM
|
ELE02-03040
| Rough-In Permanent Service | 10/16/2002 | 10/16/2002 | 10/16/2002 12:00:00 AM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 10/16/2002 at 10:59:38. Contact: ###-####. cor. posted $45.00 reinspection fee due called corrections not made and more violations created 314.43, 314.17(A) , broken clamps in 2,3,4,gang boxes 110.3(A) replace plastic boxes damaged by drilling holes in them 10/16/2002 6:16:12 PM
|
ELE02-03216
| Temporary Service | 10/16/2002 | 10/16/2002 | 10/16/2002 12:00:00 AM | P | PASS |
|
|
t/p kevin ###-####
t/s u/g new ok 10/16/2002 2:52:36 PM
|