Inspections for the day of: Thursday, October 16, 2003.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD03-01205 FIRE-Final Inspection10/15/200310/16/200310/16/2003 12:00:00 AMAFAIL
dan; Phone #: ###-#### Internet Inspection Request from: Annette Moore need emergency shut off signs on shut off valves 10/16/2003 10:57:46 AM
FIR03-00445 INSP-Alarm Testing10/15/200310/16/200310/16/2003 12:00:00 AMPPART
MIke; Phone #: ###-#### Internet Inspection Request from: Annette Moore tested first floor only and sprinkler tampers and flow - okay; this project is phased and they will occupy only the north portion of the first floor; per Dave Miller the elevator is approved without alternate floor recall due to capability of the controller; will need NFPA 72 forms; maps are completed and at fire alarm panel 10/16/2003 3:45:27 PM
FIR03-00136 INSP-Sprinkler Rough-in/Hydro10/15/200310/16/200310/16/2003 12:00:00 AMPPART
Scheduled by a contractor via Hello! on 10/15/2003 at 12:53:42 PM. Contact: ###-####.straps needed 628/609/room for construction elevator; elevator machine room requires SR heads - not QR 10/16/2003 4:03:00 PM 10/16/2003 4:03:42 PM
FIR03-00135 INSP-Sprinkler Rough-in/Hydro10/15/200310/16/200310/16/2003 12:00:00 AMPPART
Scheduled by a contractor via Hello! on 10/15/2003 at 12:54:45 PM. Contact: ###-####.Scheduled by a contractor via Hello! on 10/15/2003 at 12:53:42 PM. Contact: ###-####. straps needed 628/609/room for construction elevator; elevator machine room requires SR heads - not QR 10/16/2003 4:03:08 PM 10/16/2003 4:04:04 PM
FIR03-00115 INSP-Sprinkler Rough-in/Hydro10/15/200310/16/200310/16/2003 12:00:00 AMPPART
Scheduled by a contractor via Hello! on 10/15/2003 at 12:55:42 PM. Contact: ###-####.Scheduled by a contractor via Hello! on 10/15/2003 at 12:54:45 PM. Contact: ###-####.Scheduled by a contractor via Hello! on 10/15/2003 at 12:53:42 PM. Contact: ###-#### straps needed 628/609/room for construction elevator; elevator machine room requires SR heads - not QR 10/16/2003 4:03:14 PM 10/16/2003 4:04:12 PM
FIR03-00138 INSP-Sprinkler Rough-in/Hydro10/15/200310/16/200310/16/2003 12:00:00 AMPPART
Scheduled by a contractor via Hello! on 10/15/2003 at 12:56:35 PM. Contact: ###-####.Scheduled by a contractor via Hello! on 10/15/2003 at 12:55:42 PM. Contact: ###-####.Scheduled by a contractor via Hello! on 10/15/2003 at 12:54:45 PM. Contact: ###-####.Scheduled by a contractor via Hello! on 10/15/2003 at 12:53:42 PM. Contact: ###-####straps needed 628/609/room for construction elevator; elevator machine room requires SR heads - not QR 10/16/2003 4:03:20 PM 10/16/2003 4:04:22 PM
FIR03-00137 INSP-Sprinkler Rough-in/Hydro10/15/200310/16/200310/16/2003 12:00:00 AMPPART
Scheduled by a contractor via Hello! on 10/15/2003 at 12:57:27 PM. Contact: ###-####.Scheduled by a contractor via Hello! on 10/15/2003 at 12:56:35 PM. Contact: ###-####.Scheduled by a contractor via Hello! on 10/15/2003 at 12:55:42 PM. Contact: ###-####.Scheduled by a contractor via Hello! on 10/15/2003 at 12:54:45 PM. Contact: ###-####.Scheduled by a contractor via Hello! on 10/15/2003 at 12:53:42 PM. Contact: ###-####. straps needed 628/609/room for construction elevator; elevator machine room requires SR heads - not QR 10/16/2003 4:03:27 PM 10/16/2003 4:04:31 PM
FIR03-00139 INSP-Sprinkler Rough-in/Hydro10/15/200310/16/200310/16/2003 12:00:00 AMPPART
Scheduled by a contractor via Hello! on 10/15/2003 at 12:58:22 PM. Contact: ###-####. straps needed 628/609/room for construction elevator; elevator machine room requires SR heads - not QR 10/16/2003 4:02:51 PM
FIR03-00220 INSP-Sprinkler Rough-in10/15/200310/16/200310/16/2003 12:00:00 AMPPART
###-#### merle okay to cover rooms on north side; one room on west side shows two heads and one installed - calc room size and if over design then add head as shown on plans; heads within 1 ft of diffusers to be intermidiate temp 10/16/2003 11:07:45 AM
BLD03-01903 FIRE-Final Inspection10/16/200310/16/200310/16/2003 12:00:00 AMPCANC
ernie; Phone #: ###-#### Internet Inspection Request from: Annette Moore