Inspections for the day of: Monday, October 16, 2006.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR05-00486 INSP-Final Inspection10/13/200610/16/200610/17/2006 3:29:38 PMPFAIL
Two items on the previous correction notice dated 2/16/06 are not complete including inadequate dB in the storage room and a penthouse av which is non-functional.
FIR04-00745 INSP-Final Inspection10/13/200610/16/200610/17/2006 3:26:50 PMPFAIL
SD are overspaced in the west open area as marked on approved plans, one strobe in a north office as marked on plans is non-functional.
FIR06-00244 INSP-Final Inspection10/13/200610/16/200610/17/2006 3:24:50 PMPFAIL
Pull station is missing at the southeast exit from the TI space.
FIR06-00639 INSP-Sprinkler Rough-in10/16/200610/16/200610/16/2006 5:20:04 PMPFAIL
Inspection for the 5th floor rough-in only, one head as installed is overspaced as marked on approved plans, need to provide documentation that roofing insulation is sufficient to provide adequate freeze protection for overhead piping run in the joist channels at the deck, will need plan review verification that unsprinklered water closets are acceptable for this NFPA 13 system, overhead hydro for the 5th floor is okay, some field modifications have been made which deviate from the approved set of drawings.
FIR06-00262 INSP-Sprinkler Rough-in/Hydro10/16/200610/16/200610/16/2006 5:11:21 PMPPART
UG fire supply line is okay for cover, UG also passed hydrostatic test, noted marked locations for the FDC and WPI appear too low above finish grade.
BLD06-01980 FIRE-Final Inspection10/13/200610/16/200610/16/2006 4:52:26 PMPPASS
Fire life safety inspection passed, noted one new ductwork penetration in the north rated corridor which has not been firestopped and will need to be corrected prior to structural final, missing ceiling tile in the file storage room to be installed immediately.
FIR06-00511 INSP-Final Inspection10/16/200610/16/200610/16/2006 4:48:29 PMPPASS
Items on previous correction notice have been verified for completion, one remaining overspaced head relocated while on site, final inspection passed, permit finaled.
FIR06-00441 INSP-Sprinkler Rough-in/Hydro10/13/200610/16/200610/16/2006 12:26:48 PMAFAIL
AG hydrostatic test failed due to visible leakage and guage pressure loss.
FIR06-00608 INSP-Final Inspection10/13/200610/16/200610/16/2006 12:24:10 PMAPASS
Fire alarm work passed final inspection, permit finaled.
FIR06-00262 INSP-Sprinkler Rough-in10/16/200610/16/200610/16/2006 12:00:00 AMPCANC
bruce - note: call 1/.2 hr prior to going out 5th floor; Phone #: ###-#### Internet Inspection Request from: Patricia Smith