Inspections for the day of: Tuesday, October 16, 2007.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD07-00695 FIRE-Final Inspection10/16/200710/16/200710/16/2007 3:21:01 PMPPASS
Life safety inspection passed, noted shell permit BLD07-00693 needs to be finaled.
FIR07-00511 INSP-Final Inspection10/15/200710/16/200710/16/2007 2:07:24 PMAFAIL
See approved plans for areas defficient including overspaced heads, blocked heads, missing coverage, one pendent below max. listed distance from the deck.
BLD07-01119 FIRE-Final Inspection10/15/200710/16/200710/16/2007 1:01:26 PMPFAIL
Provide two fire extinguishers and install per review notes and discussion, manual thumbturn at the main entry/exit door is not allowed, provide approved hardware at three exit doors, EM lights and exit signs tested okay.
FIR06-00562 INSP-Final Inspection10/12/200710/16/200710/16/2007 12:57:42 PMAPART
One HD at building one elevator equip penthouse is not functional, shunt trip and voltage monitoring at bldg. 2 elevator tested okay. Need to test recall at both elevators, retest one HD, and review approved plans at next inspection.
FIR07-00600 INSP-Final Inspection10/15/200710/16/200710/16/2007 12:51:53 PMAPASS
Fire sprinkler permit work passed field inspection, permit finaled.
FIR07-00384 INSP-Final Inspection10/15/200710/16/200710/16/2007 12:51:06 PMAFAIL
Vesda system did not pass functional test.
BLD07-00980 FIRE-Final Inspection10/15/200710/16/200710/16/2007 12:49:37 PMANR
Need project related fire alarm and sprinkler permit finals prior to fire life safety approval.
FIR07-00191 INSP-Final Inspection10/10/200710/16/200710/16/2007 12:48:23 PMAFAIL
Missing pendant at one location to be added per approved plans due to overspacing.
FIR07-00328 FIR-Aging Inspection10/16/200710/16/200710/16/2007 11:47:37 AM DEFR
wip
BLD07-01239 FIRE-Final Inspection10/15/200710/16/200710/15/2007 3:12:34 PMACANC
bob - fire life safety Phone #: ###-#### Inspection cancelled from web by: Patricia Smith