BLD07-00695
| FIRE-Final Inspection | 10/16/2007 | 10/16/2007 | 10/16/2007 3:21:01 PM | P | PASS |
|
|
Life safety inspection passed, noted shell permit BLD07-00693 needs to be finaled.
|
FIR07-00511
| INSP-Final Inspection | 10/15/2007 | 10/16/2007 | 10/16/2007 2:07:24 PM | A | FAIL |
|
|
See approved plans for areas defficient including overspaced heads, blocked heads, missing coverage, one pendent below max. listed distance from the deck.
|
BLD07-01119
| FIRE-Final Inspection | 10/15/2007 | 10/16/2007 | 10/16/2007 1:01:26 PM | P | FAIL |
|
|
Provide two fire extinguishers and install per review notes and discussion, manual thumbturn at the main entry/exit door is not allowed, provide approved hardware at three exit doors, EM lights and exit signs tested okay.
|
FIR06-00562
| INSP-Final Inspection | 10/12/2007 | 10/16/2007 | 10/16/2007 12:57:42 PM | A | PART |
|
|
One HD at building one elevator equip penthouse is not functional, shunt trip and voltage monitoring at bldg. 2 elevator tested okay. Need to test recall at both elevators, retest one HD, and review approved plans at next inspection.
|
FIR07-00600
| INSP-Final Inspection | 10/15/2007 | 10/16/2007 | 10/16/2007 12:51:53 PM | A | PASS |
|
|
Fire sprinkler permit work passed field inspection, permit finaled.
|
FIR07-00384
| INSP-Final Inspection | 10/15/2007 | 10/16/2007 | 10/16/2007 12:51:06 PM | A | FAIL |
|
|
Vesda system did not pass functional test.
|
BLD07-00980
| FIRE-Final Inspection | 10/15/2007 | 10/16/2007 | 10/16/2007 12:49:37 PM | A | NR |
|
|
Need project related fire alarm and sprinkler permit finals prior to fire life safety approval.
|
FIR07-00191
| INSP-Final Inspection | 10/10/2007 | 10/16/2007 | 10/16/2007 12:48:23 PM | A | FAIL |
|
|
Missing pendant at one location to be added per approved plans due to overspacing.
|
FIR07-00328
| FIR-Aging Inspection | 10/16/2007 | 10/16/2007 | 10/16/2007 11:47:37 AM | | DEFR |
|
|
wip
|
BLD07-01239
| FIRE-Final Inspection | 10/15/2007 | 10/16/2007 | 10/15/2007 3:12:34 PM | A | CANC |
|
|
bob - fire life safety Phone #: ###-#### Inspection cancelled from web by: Patricia Smith
|