FIR06-00408
| INSP-Final Inspection | 10/16/2007 | 10/16/2007 | 10/17/2007 3:06:17 PM | P | PASS |
|
|
Permit finaled.
|
FIR03-00454
| INSP-Final Inspection | 10/16/2007 | 10/16/2007 | 10/17/2007 1:38:41 PM | P | PASS |
|
|
Permit finaled. Per the fire sprinkler contractor and the fire alarm contractor the yard PIV is on an underground line that has been abandoned.
|
FIR07-00694
| INSP-Final Inspection | 10/16/2007 | 10/16/2007 | 10/17/2007 1:01:37 PM | P | CANC |
|
|
I could not reach contractor to schedule the test. robert Phone #: ###-####
|
FIR07-00546
| FIR-Aging Inspection | 10/16/2007 | 10/16/2007 | 10/16/2007 4:46:54 PM | | NR |
|
|
Work is in progress
|
FIR06-00011
| INSP-Alarm Testing | 10/15/2007 | 10/16/2007 | 10/16/2007 4:28:34 PM | P | FAIL |
|
|
See mike timmermans notes for items tested
|
FIR07-00766
| INSP-Sprinkler Rough-in/Hydro | 10/15/2007 | 10/16/2007 | 10/16/2007 4:22:39 PM | P | FAIL |
|
|
See the city approved plans for locations where sprinkler pendants and sidewalls are overspaced. The tenting is inadequate and/or missing in many locations. Also the piping in supposed heated areas is open to unheated areas. In several locations the piping has been rerouted and additional heads have been added due to architectural features. Provide asbuilt plans prior to cover approval.
|
FIR07-00722
| INSP-Supply line flush | 10/16/2007 | 10/16/2007 | 10/16/2007 4:12:17 PM | P | PASS |
|
|
Underground supply line flush passed.
|
FIR07-00642
| INSP-Sprinkler Rough-in | 10/15/2007 | 10/16/2007 | 10/16/2007 3:56:03 PM | P | PASS |
|
|
Sales floor - areas 12 & 13 are ok to cover
|
BLD07-00277
| FIRE-Final Inspection | 10/16/2007 | 10/16/2007 | 10/16/2007 3:34:12 PM | P | FAIL |
|
|
Provide a tagged fire extinguisher in the basement and upstairs, provide an additional exit sign upstairs as discussed and shown on the approved plans and provide emergency lighting and exit sign as per the approved plans in the basement and the exterior stairwell.
|
FIR06-00438
| INSP-Sprinkler Rough-in | 10/15/2007 | 10/16/2007 | 10/16/2007 3:25:47 PM | A | CANC |
|
|
Wrong inspection called in.
|
BLD07-02089
| FIRE-Final Inspection | 10/16/2007 | 10/16/2007 | 10/16/2007 1:23:04 PM | P | FAIL |
|
|
Need the duct smoke detectors installed and tested. Need the two exit signs repaired.
|
FIR07-00859
| INSP-Final Inspection | 10/15/2007 | 10/16/2007 | 10/16/2007 1:16:55 PM | P | PASS |
|
|
The hood suppression system operated correctly.
|