Inspections for the day of: Tuesday, October 16, 2007.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00408 INSP-Final Inspection10/16/200710/16/200710/17/2007 3:06:17 PMPPASS
Permit finaled.
FIR03-00454 INSP-Final Inspection10/16/200710/16/200710/17/2007 1:38:41 PMPPASS
Permit finaled. Per the fire sprinkler contractor and the fire alarm contractor the yard PIV is on an underground line that has been abandoned.
FIR07-00694 INSP-Final Inspection10/16/200710/16/200710/17/2007 1:01:37 PMPCANC
I could not reach contractor to schedule the test. robert Phone #: ###-####
FIR07-00546 FIR-Aging Inspection10/16/200710/16/200710/16/2007 4:46:54 PM NR
Work is in progress
FIR06-00011 INSP-Alarm Testing10/15/200710/16/200710/16/2007 4:28:34 PMPFAIL
See mike timmermans notes for items tested
FIR07-00766 INSP-Sprinkler Rough-in/Hydro10/15/200710/16/200710/16/2007 4:22:39 PMPFAIL
See the city approved plans for locations where sprinkler pendants and sidewalls are overspaced. The tenting is inadequate and/or missing in many locations. Also the piping in supposed heated areas is open to unheated areas. In several locations the piping has been rerouted and additional heads have been added due to architectural features. Provide asbuilt plans prior to cover approval.
FIR07-00722 INSP-Supply line flush10/16/200710/16/200710/16/2007 4:12:17 PMPPASS
Underground supply line flush passed.
FIR07-00642 INSP-Sprinkler Rough-in10/15/200710/16/200710/16/2007 3:56:03 PMPPASS
Sales floor - areas 12 & 13 are ok to cover
BLD07-00277 FIRE-Final Inspection10/16/200710/16/200710/16/2007 3:34:12 PMPFAIL
Provide a tagged fire extinguisher in the basement and upstairs, provide an additional exit sign upstairs as discussed and shown on the approved plans and provide emergency lighting and exit sign as per the approved plans in the basement and the exterior stairwell.
FIR06-00438 INSP-Sprinkler Rough-in10/15/200710/16/200710/16/2007 3:25:47 PMACANC
Wrong inspection called in.
BLD07-02089 FIRE-Final Inspection10/16/200710/16/200710/16/2007 1:23:04 PMPFAIL
Need the duct smoke detectors installed and tested. Need the two exit signs repaired.
FIR07-00859 INSP-Final Inspection10/15/200710/16/200710/16/2007 1:16:55 PMPPASS
The hood suppression system operated correctly.