Inspections for the day of: Thursday, October 16, 2008.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE08-01977 ELE-Aging Inspection10/16/200810/16/200810/16/2008 3:29:07 PM DONE
ELE08-01977 Final10/16/200810/16/200810/16/2008 3:28:56 PMPPASS
listing ok
ELE08-01981 ELE-Aging Inspection10/16/200810/16/200810/16/2008 2:57:06 PM DONE
ELE08-01981 Final10/16/200810/16/200810/16/2008 2:56:57 PMPPASS
sign listed ok
ESC08-00615 Site Final10/16/200810/16/200810/16/2008 2:56:19 PMPPASS
site clean all landscape work complete
ELE08-02587 Permanent Service10/16/200810/16/200810/16/2008 2:12:34 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Joe Thomas p/s u/g new ok
ELE08-02268 Permanent Service10/16/200810/16/200810/16/2008 2:12:09 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Joe Thomas p/s u/g new ok
ELE08-02707 Rough-In Permanent Service10/15/200810/16/200810/16/2008 1:08:19 PMPPASS
ready for inspection Phone #: ###-#### Internet Inspection Request from: gary batten p/s o/h rec. ok
ELE08-02707 Final10/16/200810/16/200810/16/2008 1:07:58 PMPPASS
ready for inspection Phone #: ###-#### Internet Inspection Request from: gary batten ok met contr needs to seal 2 unused KOs, and bond water piping with #4, he used #6
ESC07-00513 General Inspection10/16/200810/16/200810/16/2008 12:29:23 PMPPART
ok
ELE07-01565 Electrical Rough-In10/16/200810/16/200810/16/2008 12:28:35 PMPFAIL
joe- call 1st before insp Phone #: ###-####
met owner corr needs a device for slices, wires just twisted, free length ok conductors of 6", required outlet spacing, staple cables within 8" of boxes 15 amp overcurrent for #14 AWG use manufacture's breakers sq D nail plates and 11/4" where required SABC for outlets in new pantry ,or put refer on it's own outlet
ESC08-00742 General Inspection10/16/200810/16/200810/16/2008 10:28:56 AMAPASS
site ok
ELE08-02447 Electrical Rough-In10/15/200810/16/200810/16/2008 10:28:10 AMAPASS
robert Phone #: ###-#### ok shop
ESC07-01424 General Inspection10/16/200810/16/200810/16/2008 9:48:39 AMAPASS
ok
ELE08-02230 Electrical Rough-In10/15/200810/16/200810/16/2008 9:46:43 AMAFAIL
bryan Note: if possible first in the morning Phone #: ###-#### corr met owner
make-up not done, needs concrete encased electrode, at footing 20ft #4 copper, address both subpanels, T310.15(B)(6) shall install correct size wire for 100 amp ,or use smaller size breaker , 250.148 shall grd metal boxes
ELE08-01580 Final10/15/200810/16/200810/16/2008 8:55:57 AMAPASS
Final Inspection. Please call Rick Sendra @ ###-#### prior to inspection in order to gain entrance. Phone #: ###-#### Internet Inspection Request from: Kristopher Wilson
ok survey posted 314.43 screws not allowed in plastic box kit. left of sink, 210.8 gfci outlets 6ft of laundry sink
ELE08-02230 Conference10/13/200810/16/200810/16/2008 12:00:00 AMACANC
bryan Phone #: ###-####