Inspections for the day of: Friday, October 16, 2009.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE09-02008 Conference10/15/200910/16/200910/16/2009 4:23:03 PMPDONE
Alyssa if possible please make around 3pm Thanks Please call before going out Phone #: ###-#### ok
ELE09-01913 Rough-In Permanent Service10/16/200910/16/200910/16/2009 3:18:44 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Therrin Robertson
r/i p/s u/g new ok
ELE09-01917 Rough-In Permanent Service10/16/200910/16/200910/16/2009 3:18:22 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Therrin Robertson
r/i p/s u/g new ok
ELE09-02011 Conference10/15/200910/16/200910/16/2009 2:02:15 PMPDONE
Gene-please call at least 30 mins prior to inspection Phone #: ###-#### explained NEC requirements, also owner needs to installed concrete encased electrode told him to call inspection for concrete cover, then dirt cover
ESC09-00369 General Inspection10/16/200910/16/200910/16/2009 12:13:38 PMPPASS
ok
ELE09-01285 Electrical Rough-In10/16/200910/16/200910/16/2009 12:13:03 PMPPART
Toby Groves ###-#### Oregon Tile Phone #: ###-#### Internet Inspection Request from: Debby walls soffit, hard ceilings office area, and west warehouse
ESC09-00404 General Inspection10/16/200910/16/200910/16/2009 10:22:16 AMAPART
looks ok landscape work in progress at time ok inspection
ELE09-01841 Final10/16/200910/16/200910/16/2009 10:20:59 AMPFAIL
Please inspect the parking lot lights. Thanks Phone #: ###-#### Internet Inspection Request from: ERIC called BCC no romex allowed for commercial work 334.12 (B) (4),334.30 not allowed damp wet locations, also no supportevery 41/2 ft
ELE09-02009 Electrical Rough-In10/15/200910/16/200910/16/2009 9:13:43 AMACANC
ayn Phone #: ###-#### called remove screw from inside of plastic box 314.43 contr will correct
ELE09-01991 Electrical Rough-In10/16/200910/16/200910/16/2009 7:57:56 AMAPART
u/g 2 location ok gen contr talked with city and is securing bld permit