ELE09-02008
| Conference | 10/15/2009 | 10/16/2009 | 10/16/2009 4:23:03 PM | P | DONE |
|
|
Alyssa if possible please make around 3pm Thanks Please call before going out Phone #: ###-#### ok
|
ELE09-01913
| Rough-In Permanent Service | 10/16/2009 | 10/16/2009 | 10/16/2009 3:18:44 PM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Therrin Robertson r/i p/s u/g new ok
|
ELE09-01917
| Rough-In Permanent Service | 10/16/2009 | 10/16/2009 | 10/16/2009 3:18:22 PM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Therrin Robertson r/i p/s u/g new ok
|
ELE09-02011
| Conference | 10/15/2009 | 10/16/2009 | 10/16/2009 2:02:15 PM | P | DONE |
|
|
Gene-please call at least 30 mins prior to inspection Phone #: ###-#### explained NEC requirements, also owner needs to installed concrete encased electrode told him to call inspection for concrete cover, then dirt cover
|
ESC09-00369
| General Inspection | 10/16/2009 | 10/16/2009 | 10/16/2009 12:13:38 PM | P | PASS |
|
|
ok
|
ELE09-01285
| Electrical Rough-In | 10/16/2009 | 10/16/2009 | 10/16/2009 12:13:03 PM | P | PART |
|
|
Toby Groves ###-#### Oregon Tile Phone #: ###-#### Internet Inspection Request from: Debby walls soffit, hard ceilings office area, and west warehouse
|
ESC09-00404
| General Inspection | 10/16/2009 | 10/16/2009 | 10/16/2009 10:22:16 AM | A | PART |
|
|
looks ok landscape work in progress at time ok inspection
|
ELE09-01841
| Final | 10/16/2009 | 10/16/2009 | 10/16/2009 10:20:59 AM | P | FAIL |
|
|
Please inspect the parking lot lights. Thanks Phone #: ###-#### Internet Inspection Request from: ERIC called BCC no romex allowed for commercial work 334.12 (B) (4),334.30 not allowed damp wet locations, also no supportevery 41/2 ft
|
ELE09-02009
| Electrical Rough-In | 10/15/2009 | 10/16/2009 | 10/16/2009 9:13:43 AM | A | CANC |
|
|
ayn Phone #: ###-#### called remove screw from inside of plastic box 314.43 contr will correct
|
ELE09-01991
| Electrical Rough-In | 10/16/2009 | 10/16/2009 | 10/16/2009 7:57:56 AM | A | PART |
|
|
u/g 2 location ok gen contr talked with city and is securing bld permit
|