Inspections for the day of: Tuesday, October 16, 2012.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE10-00990 ELE-Aging Inspection10/16/201210/16/201210/17/2012 3:49:39 PM DONE
Still under construction
ELE12-02566 Final10/16/201210/16/201210/16/2012 3:13:53 PMPCANC
Existing residence, Fire job Phone #: ###-#### >> Inspection requested via web by mike brown Temp service
ELE12-02566 Temporary Service10/16/201210/16/201210/16/2012 3:13:18 PMPPASS
Existing residence, Fire job Phone #: ###-#### >> Inspection requested via web by mike brown t/s u/g n ok
ELE12-02564 Electrical Rough-In10/16/201210/16/201210/16/2012 2:41:42 PMPPASS
Phone #: ###-#### >> Inspection requested via web by John VanZandt Rough in ok cover
ELE12-01291 Final10/16/201210/16/201210/16/2012 2:14:05 PMPPASS
Martin Phone #: ###-#### Final ok
GCE12-00150 GCE-Courtesy10/16/201210/16/201210/16/2012 1:46:17 PMPDONE
Darby - ###-#### Discussed requirement of up dating building wiring associated with service change and remodel
ELE12-01826 Final10/16/201210/16/201210/16/2012 12:56:16 PMPFAIL
steve Phone #: ###-#### Addition ok. NM cable ran on exterior of house from flood light to front corner must be removed or run needs to be in conduit. 334.12(B)(4)
ELE12-02448 Temporary Service10/15/201210/16/201210/16/2012 12:10:06 PMAFAIL
Inspection for temporary occupancy. Phone #: ###-#### >> Inspection requested via web by Judy Spencer 314.20 Recepticals not flush with finished surface shall have listed extender. 210.8(B)(1) Outlets in bathrooms shall have GFCI protection. 210.8(B)(5) All outlets with in 6' of a sink shall have GFCI protection. 210.8(B)(2) All 15 and 20 amp recepticals in kitchen area shall have GFCI protection. 314.25 In complete installations each box shall have a cover.
ELE12-02141 Electrical Rough-In10/15/201210/16/201210/16/2012 10:34:18 AMAPASS
Offices and front area walls, cover for underground Phone #: ###-#### >> Inspection requested via web by Patrick D Gill Rest of walls, under ground for doors and store front ceiling rough in ok cover
ELE12-02558 Conference10/15/201210/16/201210/16/2012 9:58:03 AMADONE
Please try to give me a half hour heads up. Thanks Phone #: ###-#### >> Inspection requested via web by Clay Morgan Discussed requirements for turning service back on for temp power
ELE12-02540 Rough-In Permanent Service10/15/201210/16/201210/16/2012 9:30:08 AMAPASS
Phone #: ###-#### >> Inspection requested via web by Zane Robertson Rough in ok cover p/s u/g n ok
ELE12-01783 Final10/15/201210/16/201210/16/2012 8:53:44 AMAFAIL
Phone #: ###-#### >> Inspection requested via web by Darryn Coburn Kitchen GFCI not secured to box and cover missing. Outlet in family room not working