FIR12-00609
| INSP-Conference | 10/15/2012 | 10/16/2012 | 10/19/2012 3:50:48 PM | A | DONE |
|
|
I met with Mary and went over manual pull station placement. Romeo Gervais has approved all three pull stations to be placed at the back exit door.
|
FIR12-00556
| INSP-Final Inspection | 10/16/2012 | 10/16/2012 | 10/16/2012 3:12:28 PM | P | PASS |
|
|
Permit finaled for the scope of work.
|
BLD12-01915
| FIRE-Conference | 10/16/2012 | 10/16/2012 | 10/16/2012 3:02:48 PM | P | DONE |
|
|
I spoke to the general contractor about needing to have the fire alarm system functional before final sign off and that modifications are going to be needed due to the new walls being installed which are blocking the strobe coverage.
|
FIR12-00566
| INSP-Final Inspection | 10/16/2012 | 10/16/2012 | 10/16/2012 2:20:59 PM | P | PASS |
|
|
Permit finaled
|
FIR12-00583
| INSP-Sprinkler Rough-in | 10/15/2012 | 10/16/2012 | 10/16/2012 11:43:24 AM | A | PASS |
|
|
See the city approved plans for the multiple locations where the undergorund supply lines are ok to cover. Additional fittings have been added and will need to be reflected in the overhead hydraulic calculations.
|
BLD12-02517
| FIRE-Final Inspection | 10/12/2012 | 10/16/2012 | 10/16/2012 11:39:05 AM | A | FAIL |
|
|
Insulation located at the roof deck is blocking the upright sprinkler head coverage in several locations. Also not all of the ceiling tile has been installed. All other items appear ok.
|
FIR12-00567
| INSP-Final Inspection | 10/16/2012 | 10/16/2012 | 10/16/2012 10:14:47 AM | A | PASS |
|
|
Permit finaled
|