ELE13-00837
| Electrical Rough-In | 10/16/2013 | 10/16/2013 | 10/16/2013 2:20:35 PM | P | PASS |
|
|
Mark-Partial for cover inspection Phone #: ###-#### rough-in ok cover stairwell
|
ELE13-02038
| Electrical Rough-In | 10/16/2013 | 10/16/2013 | 10/16/2013 1:57:49 PM | P | FAIL |
|
|
service inspection, Tom Gilbert is contact ###-####. thank you. Phone #: ###-#### >> Inspection requested via web by Debby Ellis NEC table 250.66 requires 1/0 cu or 3/0 alum for grounding electrode conductor to sprinkler pipe and water pipe.
|
ELE13-02363
| Final | 10/15/2013 | 10/16/2013 | 10/16/2013 1:22:54 PM | P | PASS |
|
|
Bob Phone #: ###-#### final ok
|
ELE13-02292
| Final | 10/16/2013 | 10/16/2013 | 10/16/2013 1:06:52 PM | P | FAIL |
|
|
The home should be unlocked, if not this is the CODE 6417 Phone #: ###-#### >> Inspection requested via web by Stephen Kren NEC 230(A)(2) Service disconnecting means shall not be installed in barhrooms B.C.C 04-05-31 Distribution panels shall not be installed in a bathroom,shower room, toilet room
|
ELE13-02872
| Electrical Rough-In | 10/16/2013 | 10/16/2013 | 10/16/2013 12:05:49 PM | P | PART |
|
|
Phone #: ###-#### >> Inspection requested via web by Celinda Winters partial rough-in ok cover bathrooms
|
ELE13-02864
| Electrical Rough-In | 10/15/2013 | 10/16/2013 | 10/16/2013 9:47:12 AM | A | PASS |
|
|
Contact: Garrett Collins Phone #: ###-#### >> Inspection requested via web by Deb Gooden rough-in ok cover half walls.
|
ELE13-01630
| Electrical Rough-In | 10/16/2013 | 10/16/2013 | 10/16/2013 9:13:20 AM | A | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Dan Hardisty rough-in ok cover interior demizing walls
|
ELE13-02802
| Rough-In Permanent Service | 10/15/2013 | 10/16/2013 | 10/16/2013 8:25:02 AM | A | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by daniel bibikov rough-in p/s u/g n ok 4 plex
|
ELE13-02864
| Final | 10/15/2013 | 10/16/2013 | 10/15/2013 2:36:08 PM | A | CANC |
|
|
Contact: Garrett Collins Phone #: ###-#### >> Inspection requested via web by Deb Gooden Inspection cancelled from web by: Deb Gooden
|