Inspections for the day of: Tuesday, October 16, 2018.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE14-00513 ELE-Aging Inspection10/16/201810/16/201810/23/2018 3:20:09 PM FAIL
Building permit has not been issued on this sign
ELE18-03738 Electrical Rough-In10/15/201810/16/201810/16/2018 3:21:30 PMPPASS
Aaron Phone #: ###-####
Kitchen remodel rough in ok cover
ELE18-03888 Electrical Rough-In10/16/201810/16/201810/16/2018 3:01:29 PMPPASS
underground - tony Phone #: ###-####
From house to tub pad rough in ok cover
ELE18-03571 Final10/16/201810/16/201810/16/2018 2:42:10 PMPPASS
Jay Phone #: ###-####
Service only final ok
ELE18-03964 Rough-In Permanent Service10/16/201810/16/201810/16/2018 2:09:24 PMPCANC
Call first please
Inspect trench for feeder Phone #: ###-#### Inspection requested via web by Eddy Udry
Needed underground rough in only.
ELE18-03964 Electrical Rough-In10/16/201810/16/201810/16/2018 2:09:08 PMPPASS
Call first please
Inspect trench for feeder Phone #: ###-#### Inspection requested via web by Eddy Udry
Discussed 250.32(B) equipment ground and grounding electrodes required at seperate house structure. Back window has all operable panes with no wall space to serve kitchen counter space, area to be treated as an island. Full length cabinets planned to most walls in living space shall provide floor or toe kick receptacles to serve wall space.
Underground from garage to house rough in ok cover
ELE18-03954 Electrical Rough-In10/15/201810/16/201810/16/2018 1:29:20 PMPPASS
For access please call Jamam 1/2 hr prior to inspection. ###-#### Phone #: ###-#### Inspection requested via web by Terry Scott Entertainment wall, switch for bar, cans in living room rough in ok cover
ELE18-03915 Temporary Service10/16/201810/16/201810/16/2018 12:38:00 PMAPASS
call with any questions
thank you Phone #: ###-#### Inspection requested via web by kim grundhauser t/s u/g n ok
ELE18-02622 Final10/16/201810/16/201810/16/2018 12:03:03 PMAPASS
garage code 4224
Phone #: ###-#### Inspection requested via web by Bob Glenn
Final ok
ELE18-03191 Rough-In Permanent Service10/15/201810/16/201810/16/2018 11:22:51 AMAPASS
Mucho Phone #: ###-####
Rough in ok cover p/s u/g n ok
ELE18-03393 Electrical Rough-In10/15/201810/16/201810/16/2018 10:43:17 AMAPASS
Phone #: ###-#### Inspection requested via web by Mark M
Office and exam room grid rough in ok cover
ELE18-01608 Electrical Rough-In10/15/201810/16/201810/16/2018 10:09:13 AMAPASS
Inspect pool bonding for cover. Phone #: ###-#### Inspection requested via web by Jeremy Cloud
Discussed inspections required prior to cover. A concrete encased electrode installed for building 6 and covered. Contact took pictures. This will be only time pictures will be accepted.
Discussed 250.32 ex. Seperate buildings do not require a grounding electrode if fed by a single branch circuit or a multi-wire branch circuit that have a equipment grounding conductor.
Gator and otter ponds equipotential around each and interior equipment pad rough in ok cover.