ELE19-03722
| Electrical Rough-In | 10/16/2019 | 10/16/2019 | 10/16/2019 3:59:02 PM | P | PASS |
|
|
Please call in advance if possible; 2nd floor. Phone #: ###-#### Inspection requested via web by Steve McCloy Bathroom, storage, coat rm, switch wall, walls in rooms noted rough in ok cover
|
ELE19-00602
| Electrical Rough-In | 10/16/2019 | 10/16/2019 | 10/16/2019 3:30:58 PM | P | PASS |
|
|
Cover for SE stairwell in garage. Danny is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen Level 4 S.E. stairwell rough in ok cover
|
ELE19-03543
| Electrical Rough-In | 10/15/2019 | 10/16/2019 | 10/16/2019 2:13:41 PM | P | FAIL |
|
|
Ceiling rough-in inspection Phone #: ###-#### Inspection requested via web by Kevin Perez BCC 4-05-32- Code viiolations not to be retained. * A run of 1/2" EMT leaves this panel and crow flies to front of unit is seperated at couplings and lacks secure and support for the run. 300.18- EMT shall be installed in complete runs. 358.30- In no case shall the supports and secure of EMT exceed 10'. 358.42- Couplings and connectors shall be made tight.
|
ELE19-01201
| Permanent Service | 10/16/2019 | 10/16/2019 | 10/16/2019 1:37:32 PM | P | PASS |
|
|
Please contact when done Phone #: ###-#### Inspection requested via web by Thomas wilson p/s u/g n ok
|
ELE19-01201
| Electrical Rough-In | 10/16/2019 | 10/16/2019 | 10/16/2019 1:14:35 PM | P | PASS |
|
|
Please contact when done Phone #: ###-#### Inspection requested via web by Thomas wilson Underground rough in ok cover Chassis bond ok
|
ELE19-02904
| Final | 10/16/2019 | 10/16/2019 | 10/16/2019 1:11:27 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Jeremy Cloud Final ok
|
ELE19-03788
| Final | 10/15/2019 | 10/16/2019 | 10/16/2019 11:18:11 AM | A | CANC |
|
|
Final for Temp Power Contact Pierre Elskamp Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek Needed temp service inspection. Permit will final when temp service passes.
|
ELE19-03788
| Temporary Service | 10/16/2019 | 10/16/2019 | 10/16/2019 10:38:30 AM | P | PASS |
|
|
Final for Temp Power Contact Pierre Elskamp Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek t/s u/g n ok
|
ELE18-04054
| Final | 10/15/2019 | 10/16/2019 | 10/16/2019 10:09:20 AM | A | PASS |
|
|
CONTACT: MIKE MULVAHILL Phone #: ###-#### Inspection requested via web by Deb Gooden Final ok
|
ELE19-03325
| Electrical Rough-In | 10/15/2019 | 10/16/2019 | 10/16/2019 10:08:46 AM | A | PASS |
|
|
Contact: Mike Mulvahill. ceiling inspection please Phone #: ###-#### Inspection requested via web by Deb Gooden Grid rough in ok cover.
|
ELE19-00030
| Electrical Rough-In | 10/15/2019 | 10/16/2019 | 10/16/2019 9:56:31 AM | A | PASS |
|
|
Underground, pole bases Phone #: ###-#### Inspection requested via web by Bryan Atkins West lot center planter underground and 2 pole bases rough in ok cover
|
ELE19-03928
| Rough-In Permanent Service | 10/14/2019 | 10/16/2019 | 10/16/2019 9:25:28 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Greg Traudt 300.4- Where NM cable has been run thru bored holes that do not maintain 1 1/4" from framing surface they shall be protected from damage by nail plates. Front room corner all sides, under stair above door, upper stair wall, Master bath 12-2. *Missed wiring can in kitchen near nook. *Attic boxes trimmed at rough in.
|
ELE19-02169
| Final | 10/15/2019 | 10/16/2019 | 10/16/2019 7:08:19 AM | P | CANC |
|
|
CONTACT: CINDY WOLFE Phone #: ###-#### >> Inspection requested via web by Deb Gooden Inspection cancelled from web by: Deb Gooden
|