BLD19-03790
| FIRE-Conference | 10/16/2019 | 10/16/2019 | 10/16/2019 4:25:19 PM | P | DONE |
|
|
We went over life safety requirements. I noted sprinkler modifications are needed and it appear additional emergency lights may be needed. No approved plans were on site.
|
FIR19-00752
| INSP-Sprinkler Rough-in | 10/15/2019 | 10/16/2019 | 10/16/2019 4:24:09 PM | P | PASS |
|
|
The underground supply piping is ok for cover.
UG cover. Will call when ready. Troy Phone #: ###-#### Inspection requested via web by Nathan Stenquist
|
BLD18-02802
| FIRE-Final Inspection | 10/16/2019 | 10/16/2019 | 10/16/2019 4:23:38 PM | P | PASS |
|
|
Life safety passed.
Phone #: ###-#### Inspection requested via web by Todd Landvatter
|
BLD19-02065
| FIRE-Final Inspection | 10/16/2019 | 10/16/2019 | 10/16/2019 4:22:46 PM | P | CANC |
|
|
Need the shell/core building permit finaled first. I spoke to josh about this. jOSH Phone #: ###-####
|
BLD18-01631
| FIRE-Final Inspection | 10/15/2019 | 10/16/2019 | 10/16/2019 3:09:29 PM | P | PASS |
|
|
Life safety passed. Carrie is to remove the padlock on the east side gate in the fence that the basement and second floor empty into. Carrie Phone #: ###-####
|
BLD19-04080
| FIRE-Final Inspection | 10/16/2019 | 10/16/2019 | 10/16/2019 3:02:38 PM | P | PASS |
|
|
Life safety passed. Thomas Phone #: ###-####
|
FIR18-00834
| INSP-Final Inspection | 10/15/2019 | 10/16/2019 | 10/16/2019 3:02:02 PM | P | CANC |
|
|
To be rescheduled due to time constraints due to work load.Todd Ketterling is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR19-00767
| INSP-Final Inspection | 10/15/2019 | 10/16/2019 | 10/16/2019 3:01:43 PM | P | CANC |
|
|
To be rescheduled due to time constraints due to work load. Please call Nate at ###-#### with inspection time. Phone #: ###-#### Inspection requested via web by Lori Brungardt
|
FIR19-00127
| INSP-Final Inspection | 10/16/2019 | 10/16/2019 | 10/16/2019 3:01:22 PM | P | CANC |
|
|
To be rescheduled due to time constraints due to work load. Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|
BLD18-02497
| FIRE-Final Inspection | 10/15/2019 | 10/16/2019 | 10/16/2019 3:00:56 PM | P | CANC |
|
|
To be rescheduled due to time constraints due to work load. Ken Phone #: ###-####
|
FIR19-00644
| INSP-Final Inspection | 10/16/2019 | 10/16/2019 | 10/16/2019 3:00:02 PM | P | FAIL |
|
|
No testing performed. Provide data that provide assurance that the new communicator will be maintained with-in the listed temperature range of 32 degrees to 120 degress. Also provide a smoke detector (heat may be ok) for the protection of the equipment as per NFPA 72. Drawing need to reflect the changes. Phone #: 2088990672 >> Inspection requested via mobile web by Josiah
|
FIR19-00646
| INSP-Final Inspection | 10/16/2019 | 10/16/2019 | 10/16/2019 2:59:39 PM | P | FAIL |
|
|
No testing performed. Provide data that provide assurance that the new communicator will be maintained with-in the listed temperature range of 32 degrees to 120 degress. Also provide a smoke detector (heat may be ok) for the protection of the equipment as per NFPA 72. Drawing need to reflect the changes. Phone #: 2088990672 >> Inspection requested via mobile web by Josiah
|
FIR19-00643
| INSP-Final Inspection | 10/16/2019 | 10/16/2019 | 10/16/2019 2:59:13 PM | P | FAIL |
|
|
No testing performed. Provide data that provide assurance that the new communicator will be maintained with-in the listed temperature range of 32 degrees to 120 degress. Also provide a smoke detector (heat may be ok) for the protection of the equipment as per NFPA 72. Drawing need to reflect the changes. Phone #: 2088990672 >> Inspection requested via mobile web by Josiah
|
FIR19-00639
| INSP-Final Inspection | 10/16/2019 | 10/16/2019 | 10/16/2019 2:58:45 PM | P | FAIL |
|
|
No testing performed. Provide data that provide assurance that the new communicator will be maintained with-in the listed temperature range of 32 degrees to 120 degress. Also provide a smoke detector (heat may be ok) for the protection of the equipment as per NFPA 72. Drawing need to reflect the changes. Phone #: 2088990672 >> Inspection requested via mobile web by Josiah
|
FIR19-00641
| INSP-Final Inspection | 10/16/2019 | 10/16/2019 | 10/16/2019 2:58:21 PM | P | FAIL |
|
|
No testing performed. Provide data that provide assurance that the new communicator will be maintained with-in the listed temperature range of 32 degrees to 120 degress. Also provide a smoke detector (heat may be ok) for the protection of the equipment as per NFPA 72. Drawing need to reflect the changes. Phone #: 2088990672 >> Inspection requested via mobile web by Josiah
|
FIR19-00645
| INSP-Final Inspection | 10/16/2019 | 10/16/2019 | 10/16/2019 2:57:54 PM | P | FAIL |
|
|
No testing performed. Provide data that provide assurance that the new communicator will be maintained with-in the listed temperature range of 32 degrees to 120 degress. Also provide a smoke detector (heat may be ok) for the protection of the equipment as per NFPA 72. Drawing need to reflect the changes. Phone #: 2088990672 >> Inspection requested via mobile web by Josiah
|
BLD19-00138
| FIRE-Final Inspection | 10/16/2019 | 10/16/2019 | 10/16/2019 2:29:58 PM | P | PASS |
|
|
Life safety passed. Emanuel Phone #: ###-####
|
NAF19-00048
| INSP-Final | 10/16/2019 | 10/16/2019 | 10/16/2019 2:12:01 PM | P | DONE |
|
|
Permit finaled
Call prior to going Phone #: 2088991516 >> Inspection requested via mobile web by John Looez
|
FIR18-00778
| INSP-Final Inspection | 10/14/2019 | 10/16/2019 | 10/16/2019 2:09:25 PM | A | PASS |
|
|
Permit finaled
Phone #: ###-#### Inspection requested via web by Sam Ball
|
FIR18-00867
| INSP-Final Inspection | 10/14/2019 | 10/16/2019 | 10/16/2019 2:05:34 PM | A | PASS |
|
|
Permit finaled. Phone #: ###-#### Inspection requested via web by Sam Ball
|
BLD19-03790
| FIRE-Supply Line Hydro | 10/15/2019 | 10/16/2019 | 10/16/2019 12:53:28 PM | A | CANC |
|
|
Wrong inspection type called in. Should have been conference. Terry Phone #: ###-####
|
FIR19-00531
| INSP-Sprinkler Rough-in/Hydro | 10/15/2019 | 10/16/2019 | 10/16/2019 11:20:59 AM | A | PASS |
|
|
The overhead hydro witnessed with no pressure loss. Overhead rough-in passed. I noted that the big a** fans are being installed and may cause obstruction problems. I also noted a piece of equipment being constructed that incorporates some combustible concealed spaces that will need to be addressed as well.
Call 30 mins ahead- Matt Phone #: ###-####
|
FIR18-00106
| INSP-Final Inspection | 10/15/2019 | 10/16/2019 | 10/16/2019 10:41:34 AM | A | CANC |
|
|
Call before please Thanks, Jim ###-#### Phone #: ###-#### >> Inspection requested via web by Jim Shilton Inspection cancelled from web by: Jim Shilton
|
FIR19-00337
| INSP-Final Inspection | 10/16/2019 | 10/16/2019 | 10/16/2019 10:19:30 AM | P | PASS |
|
|
Permit finaled
|
NAF18-00086
| INSP-Final | 10/15/2019 | 10/16/2019 | 10/16/2019 10:16:00 AM | A | DONE |
|
|
Permit finaled
Contact Noemi Carrero ###-#### 30 min prior to Final Insp Start please.
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
BLD19-00751
| FIRE-Final Inspection | 10/15/2019 | 10/16/2019 | 10/16/2019 9:29:27 AM | A | PASS |
|
|
Life safety passed. No card on site to sign.
7am Phone #: ###-#### Inspection requested via web by James Hibbard
|
FIR18-00957
| INSP-Conference | 10/15/2019 | 10/16/2019 | 10/16/2019 9:19:47 AM | A | DONE |
|
|
Nacho, Rick and I discussed the fire place just inside the main entry. Per Nacho he will wrap the fire place with fire treated wood to be verified by myself and the building inspector. I also noted a raised platform has been built in the south east corner of the building that wil need to be addressed as far as a combustible concealed space. Rick Phone #: ###-####
|
BLD19-00751
| FIRE-Alarm Testing | 10/15/2019 | 10/16/2019 | 10/16/2019 7:30:58 AM | A | FAIL |
|
|
Fire alarm testing needs to be scheduled with the project related FIR permit. 7am Phone #: ###-#### Inspection requested via web by James Hibbard
|
BLD19-01312
| FIRE-Conference | 10/15/2019 | 10/16/2019 | 10/16/2019 12:00:00 AM | A | DONE |
|
|
** Met with Tom. Discussed exit lighting, fire sprinkler, and fire alarm placement questions he had. He is going to meet with the architect to go over items we discussed.**MAS***Tom Phone #: ###-####
|
FIR19-00418
| INSP-Final Inspection | 10/16/2019 | 10/16/2019 | 10/16/2019 12:00:00 AM | A | FAIL |
|
|
***Failed - None of the items on the last inspection have been corrected. MAS***
Call James before heading out, thanks! Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello
|
BLD19-01233
| FIRE-Final Inspection | 10/11/2019 | 10/16/2019 | 10/11/2019 5:20:36 PM | A | CANC |
|
|
Please come first thing (7 am) so we can get done before school starts. We cant sound alarm when school in session. Thank you. Phone #: ###-#### >> Inspection requested via web by Jackie Phelps Inspection cancelled from web by: Jackie Phelps
|