Inspections for the day of: Tuesday, October 17, 2000.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR00-00543 INSP-Sprinkler Rough-in10/17/200010/17/200010/18/2000 12:00:00 AMPPART
r/i- ###-####- eric-- call after insp is completed 8 inch stubbed out 10 feet; thrust block installed at base of riser; for building 24DE 10/18/2000 9:59:45 AM
FIR00-00305 INSP-Final Inspection10/16/200010/17/200010/17/2000 12:00:00 AMAFAIL
Scheduled by a contractor via Hello! on 10/16/2000 at 13:16:35. Contact: ###-####. need to synchronize strobes in corridor 10/17/2000 10:39:46 AM
FIR00-00072 INSP-Sprinkler Rough-in10/16/200010/17/200010/17/2000 12:00:00 AMPPART
pump test don ###-#### pager tested pump for flow - okay; alarms not complete 10/18/2000 10:01:23 AM
FIR00-00275 INSP-Sprinkler Rough-in/Hydro10/16/200010/17/200010/17/2000 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 10/16/2000 at 15:46:45. Contact: ###-####. r/i and hydro okay; heads painted on 2nd floor 10/18/2000 10:00:30 AM
BLD00-00450 FIRE-Final Inspection10/17/200010/17/200010/17/2000 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 10/17/2000 at 07:46:38. Contact: ###-####.
BLD00-02229 FIRE-Final Inspection10/16/200010/17/200010/17/2000 12:00:00 AMPPASS
JESSIE-- ###-#### FIRE FN area under this permit okay; building not fully sprinklered as indicated on permit - will talk to Dan Stuart about this 10/18/2000 10:02:47 AM