Inspections for the day of: Friday, October 17, 2003.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE03-00975 ELE-Aging Inspection10/17/200310/17/200310/17/2003 12:00:00 AM CANC
no address of 2779 w apollo called no response 10/20/2003 8:43:45 AM
ELE03-01190 ELE-Aging Inspection10/17/200310/17/200310/17/2003 12:00:00 AM FAIL
called needs to support boxes so they are secured to the support , and use napproved cement, or cement fiiting better 10/20/2003 12:43:19 PM
ELE03-02125 Electrical Rough-In10/16/200310/17/200310/17/2003 12:00:00 AMAPART
CONTACT: DUANE HEINRICHS - SLAB INSPECTION; Phone #: ###-#### Internet Inspection Request from: Deb McCoy
u/g services writer's area ok 10/17/2003 10:08:46 AM
ELE03-02921 Final10/16/200310/17/200310/17/2003 12:00:00 AMACANC
CONTACT CHRIS CARMINE; Phone #: ###-#### Internet Inspection Request from: Deb McCoy called will inspect 10-20-03 10/17/2003 3:59:31 PM
ELE03-02366 Final10/16/200310/17/200310/17/2003 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 10/16/2003 at 1:48:13 PM. Contact: ###-####. ok card signed 10/17/2003 3:53:16 PM
ELE03-02550 Electrical Rough-In10/17/200310/17/200310/17/2003 12:00:00 AMPPASS
jeremy--ceiling grid; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie ok 10/17/2003 10:23:42 AM
ELE03-02356 Final10/17/200310/17/200310/17/2003 12:00:00 AMPPASS
al; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie ok 10/17/2003 11:27:49 AM
ELE03-03269 Temporary Service10/17/200310/17/200310/17/2003 12:00:00 AMPPASS
ron ###-#### t/s u/g new ok 10/17/2003 11:27:33 AM
ELE03-03272 Electrical Rough-In10/17/200310/17/200310/17/2003 12:00:00 AMPPART
dan ###-####--end unit on 14 r/i ok p/s still in violation, no violations to be retained 10/17/2003 5:03:51 PM
ELE03-02509 Final10/17/200310/17/200310/17/2003 12:00:00 AMPPASS
MIKE; Phone #: ###-#### Internet Inspection Request from: Annette Moore ok 10/17/2003 12:16:04 PM
ELE03-03249 Final10/17/200310/17/200310/17/2003 12:00:00 AMPPASS
PAT; Phone #: ###-#### Internet Inspection Request from: Annette Moore ok 10/17/2003 1:00:49 PM
ELE03-02848 Final10/17/200310/17/200310/17/2003 12:00:00 AMPFAIL
###-####--gary cor. posted called wiremold shall be installed to meet386.100 , 250.148 grd all boxes, 110.12(A) seal all unused openings, 300.14 needs 6" free length conductor at all outets and j boxes, use approved fittings for plug mold not duct tape, no violations to be retained isolate grds and neutrals at sub panel, shall not ID 6 or samller neutral, 10/17/2003 1:59:43 PM
ELE03-03104 Permanent Service10/17/200310/17/200310/17/2003 12:00:00 AMPPASS
will be ready for reinspection around 2:00 thanks.; Phone #: ###-#### Internet Inspection Request from: Andy Rose
p/s o/h rec. ok 10/17/2003 2:33:51 PM