Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR03-00469 INSP-Final Inspection10/16/200310/17/200310/17/2003 12:00:00 AMAFAIL
No inspection done due to work not matching plans and work done without a permit. A new FM200 suppression system has been connected to the existing fire alarm system. This work is not shown on the approved fire alarm system. Lea Electric admitted to installing the wiring between the zoned panel and the releasing panel but no contractor will admitt to who did the interconnection. I spoke to Dave Miller. A pre-citation lette will be issued and if appropriate a citation will be issued. 10/17/2003 11:23:02 AM