ELE05-03742
| Electrical Rough-In | 10/17/2005 | 10/17/2005 | 10/17/2005 4:40:41 PM | P | DONE |
|
|
For Approval of Cover; Phone #: ###-#### x114 Internet Inspection Request from: Jim Woodhead done Friday by 336.
|
ELE05-03347
| Final | 10/17/2005 | 10/17/2005 | 10/17/2005 3:36:27 PM | P | PASS |
|
|
please call 30 min b4 so can let you in//TOLLY; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa ok to final
|
ELE05-03648
| Rough-In Permanent Service | 10/14/2005 | 10/17/2005 | 10/17/2005 2:37:50 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 10/14/2005 at 12:22:01 PM. Contact: ###-####. ric ok, p/s u/g n ok
|
ELE05-03635
| Permanent Service | 10/14/2005 | 10/17/2005 | 10/17/2005 2:19:17 PM | P | PASS |
|
|
shane; Phone #: ###-#### Internet Inspection Request from: Barbara Moore ric kitchen only ok, p/s u/g n ok
|
ELE05-03748
| Final | 10/17/2005 | 10/17/2005 | 10/17/2005 1:37:00 PM | P | FAIL |
|
|
chuck; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa ok to cover u/g, 408.7 unused openings shall be closed in service.
|
ELE05-03732
| Conference | 10/14/2005 | 10/17/2005 | 10/17/2005 10:22:26 AM | A | CANC |
|
|
please call 30 min prior to meet you///bob; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa see ri
|
ELE05-03177
| Final | 10/14/2005 | 10/17/2005 | 10/17/2005 9:15:51 AM | A | PASS |
|
|
Charlie; Phone #: ###-#### Internet Inspection Request from: Melyne Davis ok to final
|
ELE05-03104
| Final | 10/14/2005 | 10/17/2005 | 10/17/2005 9:11:16 AM | A | FAIL |
|
|
READY FOR FINAL INSPECTION FOR THE UPSTAIRS FOR OCCUPANCY. YOU CAN CONTACT THE CONTRACTOR ON HIS CELL PHONE AT ###-####. THANK YOU.; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH called contr, left correction notice, 404.9 switches shall have faceplates, 406.4 recpt shall be securely fastened,406.5 recpts shall have faceplates, 406.8(E) floor recpts shall have weatherproof covers, 314.25 boxes shall have covers, 110.12(C) there shall be no broken parts, 110.3 recpts shall be installed correctly,i.e. no hot and gnd reversed, no hots on neutrals, front recpts shalll operate, 210.8(B) gfci recpts shall be provided by sinks
|
ELE05-03178
| Final | 10/14/2005 | 10/17/2005 | 10/17/2005 8:05:02 AM | A | PASS |
|
|
Charlie; Phone #: ###-#### Internet Inspection Request from: Melyne Davis ok to final
|
ELE05-03732
| Electrical Rough-In | 10/17/2005 | 10/17/2005 | 10/17/2005 12:00:00 AM | A | FAIL |
|
|
please call 30 min prior to meet you///bob; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa called owner, did conference and r/i since he did over weekend anyway. left corr notice, 312.5 conductors entering enclosure shall have abrasion protection,200.6(B) id shall be provided for grounded conductor, 250.110 metal boxes shall be grounded, 334.30 nm cable shall be stapled within 12 " of box, BCC all make-up shall be done, u/g shall be inspected before cover.
|