Inspections for the day of: Tuesday, October 17, 2006.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-00921 ELE-Aging Inspection10/17/200610/17/200610/24/2006 7:14:35 AM CANC
ELE06-00422 Electrical Rough-In10/17/200610/17/200610/17/2006 4:30:32 PMPCANC
this is for the 1s floor, any questions pleae call Steve Nuxoll - he will be on the 1st floor, phone sometime doesn't work; Phone #: ###-#### Internet Inspection Request from: Jeff Radford Steve called will do inspection 10-18-06 AM
ELE06-03824 Rough-In Permanent Service10/16/200610/17/200610/17/2006 4:29:39 PMPFAIL
Scheduled by a contractor via Hello! on 10/16/2006 at 11:15:26 PM. Contact: ###-####. corr. called 250.104(A)(1) shall bond copper piping with #2 copper, 314.16 box fill, 210.52(A) outlet spacing missing wall in basement theater, 314.17(C) replace all 2,3,4, gang boxes broken out clamps, 300.4 nail plates and 11/4"
ELE06-03845 Permanent Service10/16/200610/17/200610/17/2006 3:36:41 PMPFAIL
Phone #: ###-#### Internet Inspection Request from: Lee VanSchoiack
corr. called left message, 300.4 nail plates and 11/4", 314.3&110.3(B) bond bushings for metal raceways in plastic boxes 300.10 bond bushings where RE washers are used, 330.30 & 348.30 strap MC and flex within 12" of everything,250.122T needs #10 equip grd at 4sq. for 50 amp circuit
ELE06-03798 Rough-In Permanent Service10/17/200610/17/200610/17/2006 1:32:39 PMPFAIL
reinspection; Phone #: ###-#### Internet Inspection Request from: DJ Carman corr. fee due called, 300.4(A)(1)&(D) nail plates and 11/4" for cables parallel, 334.30 staple cables 12" or 8" as code states, 314.43 no screws in plastic boxes, note grd or bond new p/s to water system old part of house, 250.52(A)(1) or 104(A)(1)
ELE06-03692 Rough-In Permanent Service10/16/200610/17/200610/17/2006 12:46:58 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Tracy Robertson r/i ok all 4 units, p/s u/g new ok
ELE06-03683 Permanent Service10/16/200610/17/200610/17/2006 10:50:39 AMAPASS
rick; Phone #: ###-#### Internet Inspection Request from: Patricia Smith p/s u/g rec. ok
ELE06-03830 Temporary Service10/16/200610/17/200610/17/2006 10:21:02 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Zane Robertson t/s o/h new ok
ELE06-03847 Electrical Rough-In10/17/200610/17/200610/17/2006 9:47:50 AMAFAIL
Give me a call if any questions Thanks; Phone #: ###-#### Internet Inspection Request from: Don Lustig corr. called left message, 314.16 box fill old 3 gang N wall by door kit, 300.14 6" free length where work was done in old and new areas, 300.4 nail plates and 11/4" for cables parallel
ELE06-03224 Final10/16/200610/17/200610/17/2006 9:23:25 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Lee ok
ELE06-02053 ELE-Aging Inspection10/17/200610/17/200610/17/2006 8:46:38 AM PART
wsuc
ELE06-03803 Temporary Service10/16/200610/17/200610/17/2006 8:46:11 AMAPASS
Internet Inspection Request from: Rowdy Monroe t/s u/g new ok
ELE06-03804 Temporary Service10/16/200610/17/200610/17/2006 8:45:46 AMAPASS
Internet Inspection Request from: Rowdy Monroe t/s u/g new ok
ELE06-03802 Temporary Service10/16/200610/17/200610/17/2006 8:45:25 AMAPASS
Internet Inspection Request from: Rowdy Monroe t/s u/g new ok
ELE06-03801 Temporary Service10/16/200610/17/200610/17/2006 8:45:03 AMAPASS
Internet Inspection Request from: Rowdy Monroe t/s u/g new ok