Inspections for the day of: Wednesday, October 17, 2007.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-02781 Rough-In Permanent Service10/17/200710/17/200710/17/2007 3:15:52 PMPCANC
Mike Phone #: ###-#### called contr will reschedule
ELE07-00776 Final10/17/200710/17/200710/17/2007 2:33:02 PMPFAIL
zack - please call for access Phone #: ###-#### called twice left message no response back
ELE07-03545 Rough-In Permanent Service10/17/200710/17/200710/17/2007 2:06:07 PMPPASS
jean Phone #: ###-#### r/i p/s u/g new ok
ELE07-02346 Final10/17/200710/17/200710/17/2007 1:17:13 PMPFAIL
Greg ###-#### corr. called left message, all wiring for dental hanging fixtures and cabinets shall meet 517.13A&B, no flex allowed, 330.30 secure all mc cables every 6ft and 12" of boxes in crawl space, 314.23 secure all boxes in dental cabinets
ELE07-02482 Final10/17/200710/17/200710/17/2007 12:08:06 PMPPASS
ELE07-02486 Final10/17/200710/17/200710/17/2007 12:07:37 PMPPASS
ELE07-01308 Electrical Rough-In10/16/200710/17/200710/17/2007 10:24:54 AMAPASS
Inspect underground for backfill for motorized gate at east entry. Electrician Brian ###-####. Thank you. Phone #: ###-#### Internet Inspection Request from: Carla Ward ok
ELE05-02576 Final10/16/200710/17/200710/17/2007 9:36:56 AMAPASS
jim - please call 1/2 hr prior to inspection Phone #: ###-#### ok
ELE07-03539 Electrical Rough-In10/16/200710/17/200710/17/2007 8:36:45 AMAPASS
gary Note:please call 1/2 hr prior to inspection Phone #: ###-#### ok fam. rm.
ELE05-04072 Final10/16/200710/17/200710/17/2007 8:36:18 AMAPASS
ok