FIR14-00344
| INSP-Sprinkler Rough-in | 10/16/2014 | 10/17/2014 | 10/17/2014 5:20:17 PM | P | PART |
|
|
Rough-in at building C 2nd floor completed. Items noted include; overspaced SW head at unit C206, coverage at mechanical, trash and storage rooms overspaced- install per design, plan modification necessary for field changes to 2" main and branchline layout, housekeeping room and 2" main in the corridor not yet installed. Previous C/N items done.
|
BLD14-00126
| FIRE-Final Inspection | 10/17/2014 | 10/17/2014 | 10/17/2014 4:11:51 PM | P | PASS |
|
|
|
FIR14-00531
| INSP-Conference | 10/17/2014 | 10/17/2014 | 10/17/2014 4:06:56 PM | A | PART |
|
|
|
FIR14-00686
| INSP-Final Inspection | 10/17/2014 | 10/17/2014 | 10/17/2014 2:22:28 PM | P | NR |
|
|
please call 1/2hour prior please Phone #: ###-#### Inspection requested via web by Rick Groom
|
FIR14-00639
| INSP-Sprinkler Rough-in | 10/17/2014 | 10/17/2014 | 10/17/2014 1:50:14 PM | P | PART |
|
|
Okay to cover remainder of fire sprinkler work at the core group of rooms with grid ceilings as marked and dated on approved plan. Need to provide a ceiling or extend walls to the deck at the mechanical room.
|
BLD14-00126
| FIRE-Final Inspection | 10/17/2014 | 10/17/2014 | 10/17/2014 12:17:01 PM | A | PASS |
|
|
Fire life safety finaled.
|
FIR14-00593
| INSP-Final Inspection | 10/17/2014 | 10/17/2014 | 10/17/2014 12:15:06 PM | A | PASS |
|
|
Inspection passed. Fire alarm permit finaled.
|
FIR14-00637
| INSP-Final Inspection | 10/17/2014 | 10/17/2014 | 10/17/2014 12:14:20 PM | A | PASS |
|
|
Fire alarm work passed inspection. Permit finaled.
|