Inspections for the day of: Tuesday, October 17, 2017.
Number of inspections: 9
Percentage of inspections complete: 89 %
Percentage of inspections not complete: 11 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR15-00382 INSP-Conference10/11/201710/16/2017 A 
Follow up with Colton
FIR16-00446 INSP-Final Inspection10/17/201710/17/201710/17/2017 2:26:31 PMPFAIL
Todays inspection was an initial walk through. I noted that there are two missing horn/strobes in the basement (and a room), one strobe in the basement has been set at 110cd instead of 75cd as shown on the plans, first floor horn/strobes in the south building are incorrectly set at 75cd instead of 15cd, the south building second floor horn/strobe is located too far from the end of the corridor, not all of the fire/smoke dampers have been provided access for verification of correct closure, none of the elevator fire doors are installed, need map, basement manual pull station is mounted too high. We set off the horn, strobes and found that nothing is sync'ing as required by NFPA 72. As-builts are needed showing the changes and will need to be approved by the engineer of record. No actual testing of devices was performed at this time.

Greg Phone #: ###-####
FIR16-00284 INSP-Sprinkler Rough-in/Hydro10/17/201710/17/201710/17/2017 2:19:09 PMPFAIL
Hydro test of the dry system failed due to visible loss of pressure at the guage.
BLD17-03466 FIRE-Final Inspection10/17/201710/17/201710/17/2017 2:18:14 PMPFAIL
Provide re-certification of the hood suppression system, mount the fire extinguishers, repair the exit signs/emergency lights.

Danielle Phone #: ###-####
BLD17-01371 FIRE-Final Inspection10/17/201710/17/201710/17/2017 11:37:35 AMPPASS
Life safety passed

Jason Phone #: ###-####
FIR17-00261 INSP-Final Inspection10/17/201710/17/201710/17/2017 11:37:14 AMPPASS
Permit finaled
FIR17-00318 INSP-Final Inspection10/17/201710/17/201710/17/2017 11:29:44 AMPPASS
Permit finaled

Colton Phone #: ###-####
FIR17-00365 INSP-Sprinkler Rough-in/Hydro10/16/201710/17/201710/17/2017 9:13:39 AMACANC
Not ready for a hydro due to a leaking flange
FIR17-00433 INSP-Sprinkler Rough-in/Hydro10/16/201710/17/201710/16/2017 11:43:00 AMACANC
Contact Scott Powada ###-#### 30 min prior to Hydro insp start please

Thank YOU Phone #: ###-#### >> Inspection requested via web by Teri Cruickshank Inspection cancelled from web by: Teri Cruickshank