FIR15-00382
| INSP-Conference | 10/11/2017 | 10/16/2017 | | A | |
|
|
Follow up with Colton
|
FIR16-00446
| INSP-Final Inspection | 10/17/2017 | 10/17/2017 | 10/17/2017 2:26:31 PM | P | FAIL |
|
|
Todays inspection was an initial walk through. I noted that there are two missing horn/strobes in the basement (and a room), one strobe in the basement has been set at 110cd instead of 75cd as shown on the plans, first floor horn/strobes in the south building are incorrectly set at 75cd instead of 15cd, the south building second floor horn/strobe is located too far from the end of the corridor, not all of the fire/smoke dampers have been provided access for verification of correct closure, none of the elevator fire doors are installed, need map, basement manual pull station is mounted too high. We set off the horn, strobes and found that nothing is sync'ing as required by NFPA 72. As-builts are needed showing the changes and will need to be approved by the engineer of record. No actual testing of devices was performed at this time.
Greg Phone #: ###-####
|
FIR16-00284
| INSP-Sprinkler Rough-in/Hydro | 10/17/2017 | 10/17/2017 | 10/17/2017 2:19:09 PM | P | FAIL |
|
|
Hydro test of the dry system failed due to visible loss of pressure at the guage.
|
BLD17-03466
| FIRE-Final Inspection | 10/17/2017 | 10/17/2017 | 10/17/2017 2:18:14 PM | P | FAIL |
|
|
Provide re-certification of the hood suppression system, mount the fire extinguishers, repair the exit signs/emergency lights.
Danielle Phone #: ###-####
|
BLD17-01371
| FIRE-Final Inspection | 10/17/2017 | 10/17/2017 | 10/17/2017 11:37:35 AM | P | PASS |
|
|
Life safety passed
Jason Phone #: ###-####
|
FIR17-00261
| INSP-Final Inspection | 10/17/2017 | 10/17/2017 | 10/17/2017 11:37:14 AM | P | PASS |
|
|
Permit finaled
|
FIR17-00318
| INSP-Final Inspection | 10/17/2017 | 10/17/2017 | 10/17/2017 11:29:44 AM | P | PASS |
|
|
Permit finaled
Colton Phone #: ###-####
|
FIR17-00365
| INSP-Sprinkler Rough-in/Hydro | 10/16/2017 | 10/17/2017 | 10/17/2017 9:13:39 AM | A | CANC |
|
|
Not ready for a hydro due to a leaking flange
|
FIR17-00433
| INSP-Sprinkler Rough-in/Hydro | 10/16/2017 | 10/17/2017 | 10/16/2017 11:43:00 AM | A | CANC |
|
|
Contact Scott Powada ###-#### 30 min prior to Hydro insp start please
Thank YOU Phone #: ###-#### >> Inspection requested via web by Teri Cruickshank Inspection cancelled from web by: Teri Cruickshank
|