Inspections for the day of: Wednesday, October 17, 2018.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorChad Schwendiman
TitleMEC-INSPECTOR
Phone #780-9549
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC18-05003 Pressure Test10/17/201810/17/201810/17/2018 4:01:46 PMPPASS
job should be ready around 2
call many 20 min in advance thanks Phone #: ###-#### Inspection requested via web by Manuel Canto - 20lb gas pass
MEC18-00631 Rough-in10/17/201810/17/201810/17/2018 3:29:11 PMPPART
if questions call Glen ###-####. Phone #: ###-#### Inspection requested via web by Stacia Haumann - Condensate piping in the walls okay in rooms 205, 210, 219
MEC18-03085 Final10/17/201810/17/201810/17/2018 3:16:56 PMPPASS
call for access- Ken Phone #: ###-####
MEC18-04550 Final10/11/201810/17/201810/17/2018 2:46:10 PMPPASS
Phone #: ###-#### Inspection requested via web by Mary LaFayette
MEC18-03485 Final10/17/201810/17/201810/17/2018 2:10:01 PMPPASS
Field Super: Daryl Thomas Phone #: ###-#### Inspection requested via web by Lisa Whitney
MEC18-04548 Pressure Test10/17/201810/17/201810/17/2018 1:51:26 PMPPASS
Field super: Daryl Thomas Phone #: ###-#### Inspection requested via web by Lisa Whitney - 20lb gas
MEC18-04548 Rough-in10/17/201810/17/201810/17/2018 1:50:44 PMPNR
Field super: Daryl Thomas Phone #: ###-#### Inspection requested via web by Lisa Whitney
MEC18-04694 Rough-in10/16/201810/17/201810/17/2018 11:24:19 AMAPASS
Phone #: ###-#### Inspection requested via web by Ashley Stegemann
MEC18-04984 Rough-in10/16/201810/17/201810/17/2018 10:33:45 AMAPASS
We will be there finishing up all morning Inspection requested via web by jeff jedlick
MEC18-04984 Pressure Test10/17/201810/17/201810/17/2018 10:33:32 AMAPASS
We will be there finishing up all morning Inspection requested via web by jeff jedlick - 20lb gas
MEC18-04602 Pressure Test10/16/201810/17/201810/17/2018 9:48:50 AMAPASS
pressure witness - call david Phone #: ###-#### Inspection requested via web by Brandon Sorensen - 20lb gas, 5lb flue
MEC18-04602 Rough-in10/16/201810/17/201810/17/2018 9:43:04 AMAFAIL
rough - call david Phone #: ###-#### Inspection requested via web by Brandon Sorensen - Need to complete range vent, Need approved manual J onsite.
MEC18-04988 Pressure Test10/16/201810/17/201810/17/2018 9:18:20 AMAFAIL
Gas pressure test Phone #: ###-#### Inspection requested via web by Jamee Shoecraft - Need to pressuer test gas piping at minimum of 20lbs on a 30lb gauge or 60lbs on a 100lb gauge. Need to presurre test underground gas pipung and install 18ga. yellow tracer wire.