Inspections for the day of: Tuesday, October 18, 2005.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-03765 Temporary Service10/17/200510/18/200510/19/2005 10:29:49 AMAPASS
charlie ###-#### t/s u/g new ok
ELE05-03745 Permanent Service10/18/200510/18/200510/18/2005 3:31:10 PMPFAIL
write corrections that single meter to be installed and sub panels be brought up to code. cor posted called
ELE05-03582 Permanent Service10/18/200510/18/200510/18/2005 2:52:58 PMPFAIL
write corrections to change to single meter and make sub panels meet code cor. posted only 1 meter and all wiring shall meet current NEC called
ELE05-03486 Electrical Rough-In10/18/200510/18/200510/18/2005 2:07:39 PMPPASS
rough in new bathroom; Phone #: ###-#### Internet Inspection Request from: Andy Rose ok called outlet on wall shall be on bathrm circuit
ELE05-02356 Conference10/17/200510/18/200510/18/2005 1:28:13 PMPDONE
please call 1 hour prior so can meet you//jack; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa
ELE05-02596 ELE-Aging Inspection10/18/200510/18/200510/18/2005 12:50:42 PM PART
called WSUC
ELE05-03764 Temporary Service10/17/200510/18/200510/18/2005 10:30:33 AMAFAIL
charlie ###-#### called terminate GEC to neutral bus
ELE05-03784 Temporary Service10/17/200510/18/200510/18/2005 10:05:41 AMAFAIL
Charlie Internet Inspection Request from: Melyne Davis called terminate GEC at neutral bus
ELE05-03767 Temporary Service10/17/200510/18/200510/18/2005 10:05:00 AMAFAIL
charlie ###-#### called terminate GEC at neutral bus
ELE05-03745 Permanent Service10/17/200510/18/200510/18/2005 8:57:42 AMAPASS
brandon; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa
p/s u/g new ok
ELE05-03185 Rough-In Permanent Service10/17/200510/18/200510/18/2005 8:29:45 AMAPART
Scheduled by a contractor via Hello! on 10/17/2005 at 9:37:25 AM. Contact: ###-####. r/i ok only called has line from meter on load side of breaker
ELE05-02356 Final10/18/200510/18/200510/18/2005 12:00:00 AMPPASS
please call 1 hour prior so can meet you//jack; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa
final ok fixtures in MB closet corrected
ELE05-03766 Temporary Service10/17/200510/18/200510/17/2005 4:22:32 PMACANC
charlie ###-#### Inspection cancelled from web by: Melyne Davis