Inspections for the day of: Tuesday, October 18, 2011.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR11-00534 INSP-Sprinkler Rough-in10/18/201110/18/201110/18/2011 4:16:26 PMPPART
Regarding plan notes for bollards at the new PIV- to be installed per discussion.
FIR11-00388 INSP-Final Inspection10/18/201110/18/201110/18/2011 4:13:36 PMPPEND
Final pending elevator hat functions.
FIR11-00546 INSP-Sprinkler Rough-in10/18/201110/18/201110/18/2011 4:12:50 PMPPART
Overhead work approved for cover with the exception of patient room #1 (no access) and missing coverage at a communications closet. See plans for marked and dated areas.
BLD11-01354 FIRE-Final Inspection10/18/201110/18/201110/18/2011 2:00:41 PMPPASS
Fire life safety final okayed.
BLD09-02234 FIRE-Final Inspection10/17/201110/18/201110/18/2011 1:58:21 PMAPASS
Verified PFE's have been provided as discussed. Life safety passed.
BLD11-01171 FIRE-Final Inspection10/17/201110/18/201110/18/2011 1:19:57 PMAFAIL
Incompleted correction items include; post building address, remove exposed paper faced insulation at the ceiling joists, exit signage at one door needs relocated.