ELE16-03224
| Electrical Rough-In | 10/18/2016 | 10/18/2016 | 10/18/2016 2:27:17 PM | P | PASS |
|
|
Please call Gabe (###-####) 30 minutes ahead. Phone #: ###-#### Inspection requested via web by Brad Girard floor heat only ok to cover
|
ELE16-02151
| Final | 10/18/2016 | 10/18/2016 | 10/18/2016 12:09:50 PM | P | PASS |
|
|
Phone #: ###-#### Final ok
|
ELE16-00752
| Final | 10/17/2016 | 10/18/2016 | 10/18/2016 12:02:05 PM | A | PART |
|
|
units 118 120 Phone #: ###-#### Inspection requested via web by Tracy Robertson units listed final ok
|
ELE16-00751
| Final | 10/17/2016 | 10/18/2016 | 10/18/2016 10:21:32 AM | A | PART |
|
|
units 101 103 105 111 112 Phone #: ###-#### Inspection requested via web by Tracy Robertson Listed units final ok
|
ELE16-02857
| Electrical Rough-In | 10/17/2016 | 10/18/2016 | 10/18/2016 9:22:08 AM | A | FAIL |
|
|
Sean is contact. Partial ceiling inspection Phone #: ###-#### Inspection requested via web by Ryan Wake 300.11. Cables shall not be suppoted by ceiling grid. 314.17 A openings shall be closed. (2 junction boxes near entry)
|