Inspections for the day of: Tuesday, October 18, 2016.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJames Ady
TitleELE-INSPECTOR
Phone #914-4683
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE16-03224 Electrical Rough-In10/18/201610/18/201610/18/2016 2:27:17 PMPPASS
Please call Gabe (###-####) 30 minutes ahead. Phone #: ###-#### Inspection requested via web by Brad Girard floor heat only ok to cover
ELE16-02151 Final10/18/201610/18/201610/18/2016 12:09:50 PMPPASS
Phone #: ###-#### Final ok
ELE16-00752 Final10/17/201610/18/201610/18/2016 12:02:05 PMAPART
units 118 120 Phone #: ###-#### Inspection requested via web by Tracy Robertson units listed final ok
ELE16-00751 Final10/17/201610/18/201610/18/2016 10:21:32 AMAPART
units 101 103 105 111 112 Phone #: ###-#### Inspection requested via web by Tracy Robertson Listed units final ok
ELE16-02857 Electrical Rough-In10/17/201610/18/201610/18/2016 9:22:08 AMAFAIL
Sean is contact. Partial ceiling inspection Phone #: ###-#### Inspection requested via web by Ryan Wake 300.11. Cables shall not be suppoted by ceiling grid. 314.17 A openings shall be closed. (2 junction boxes near entry)